Shelf Manager CLI
# clia activate 90 0
Pigeon Point Shelf Manager Command Line Interpreter
Command issued via IPMB, status = 0 (0x0)
Command executed successfully

alarm

clia alarm [clear | info| minor | major | critical]
This command provides access to the TELCO alarm outputs.
Enter
clia alarm without parameters to view the current status of TELCO alarm outputs:
# clia alarm
Pigeon Point Shelf Manager Command Line Interpreter
alarm mask: 0x00
Alarm mask 0x00 means no alarm.
Clearing alarms
Enter
clia alarm clear to clear the minor and major alarm outputs. By default, critical alarm outputs can be
cleared because the
# ALLOW_CLEARING_CRITICAL_ALARM: This parameter of boolean type enables the
# ability to clear the critical alarm condition without the alarm cutoff
# button. Default is FALSE.
#
ALLOW_CLEARING_CRITICAL_ALARM = TRUE
If you change
ALLOW_CLEARING_CRITICAL_ALARM to FALSE the clia alarm clear command does not
clear critical alarms.
Enter
clia alarm info to display information about the last alarm that occurred:
# clia alarm info
Pigeon Point Shelf Manager Command Line Interpreter
Last saved alarm information:
Alarm mask: 0x00
    Alarm date/time: Sun Jun 8 21:56:47 2009
    Alarm source: Schroff Carrier
    Alarm reason: Cooling state alert
FortiGate-5144C 6.2.3 Chassis Guide
shelfman.conf file contains the following lines:
Clearing the alarm changes the information displayed by the
the information displayed by the
clia alarm info command
Fortinet Technologies Inc.
clia alarm command but not