List And Description Of Alarms On Display - Lennox e-MovAir Series Installation & Operating Manual

Packaged air handling unit
Table of Contents

Advertisement

e-MovAir-IOM-20.04-EN

13.0. LIST AND DESCRIPTION OF ALARMS ON DISPLAY

ALARM
ALARMS
NUMBER
1
Clock Alarm
2
Memory Alarm
3
Alarm U1
4
Alarm U2
5
Alarm U3
6
Alarm U4
7
Alarm U5
8
Alarm U6
9
Alarm U7
10
Alarm U8
11
Safety Damper Open
12
Smoke-fire Alarm
13
Dirty filter warning
14
Dirty filter Alarm
15
Fans thermal prot.
16
Alarm U9
17
Alarm U10
18
Alarm U11
19
Alarm U12
20
21
Compr. 1 thermal prot.
22
Low press. switch c1
23
High press. switch c1
24
Too many low sw c1
25
Too many high sw c1
26
Out of Enevelope c1
27
Too many out Envel. c1
28
High press. elec. c1
29
Too many high elec. c1
30
out of limit time c1
31
Too many out limit c1
32
Low press. elec. c1
33
Too many low elec. c1
34
35
36
37
e-MovAir-IOM-20.04-EN
ALARMS DESCRIPTION
Clock PCO Alarm
Internal memory Alarm
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Safety damper not opened after movement
time
Doors, fire, smoke sensor alarm
Filter warning
Filter alarm
Fans thermal protection
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Probe broken or disconnected
Compressor 1 thermal protection
Low pressure switch circuit 1
High pressure switch circuit 1
Too many low pressure switch alarm in
monitor time
Too many high pressure switch alarm in
monitor time
Compressor work out of envelope
Too many out of enevelope alarm in monitor
time
Condensation pressure over threshold circuit
1
Too many condensation pressure over
threshold in monitor time
Compressor is working out of limit for long
time
Too many compressor out of limit in monitor
time
Evaporation pressure under threshold circuit
1
Too many evaporation pressure under
threshold in monitor time
26
REARM
Manual
Manual strong (5 seconds
alarm button pressed)
Auto
Auto
Auto
Auto
Auto
Manual strong
Manual strong
Auto
Manual strong
Auto
Manual strong
Auto
Manual strong
Auto
Manual strong
www.lennoxemea.com