e-MovAir-IOM-20.04-EN
ALARM
ALARMS
NUMBER
38
39
40
Compr. 2 thermal prot.
41
Compr. 3 thermal prot.
42
Low press. switch c2
43
High press. switch c2
44
Too many low sw c2
45
Too many high sw c2
46
Out of Enevelope c2
47
Too many out Envel. c2
48
High press. elec. c2
49
Too many high elec. c2
50
out of limit time c2
51
Too many out limit c2
52
Low press. elec. c2
53
Too many low elec. c2
54
55
56
57
58
59
60
Safety thermostat
61
electrical heater 1
62
electrical heater 2
63
Burner protection 1
64
Burner protection 2
65
66
67
68
69
70
71
72
e-MovAir-IOM-20.04-EN
ALARMS DESCRIPTION
Compressor 2 thermal protection
Compressor 3 thermal protection
Low pressure switch circuit 2
High pressure switch circuit 2
Too many low pressure switch alarm in
monitor time
Too many high pressure switch alarm in
monitor time
Compressor work out of envelope
Too many out of enevelope alarm in monitor
time
Condensation pressure over threshold circuit
2
Too many condensation pressure over
threshold in monitor time
Compressor is working out of limit for long
time
Too many compressor out of limit in monitor
time
Evaporation pressure under threshold circuit
2
Too many evaporation pressure under
threshold in monitor time
External safety thermostat alarm
Electrical heater 1 thermal protection
Electrical heater 2 thermal protection
Burner 1 thermal protection
Burner 2 thermal protection
27
REARM
Auto
Auto
Manual strong
Manual strong
Auto
Manual strong
Auto
Manual strong
Auto
Manual strong
Auto
Manual strong
Auto
Auto
Auto
Auto
Auto
www.lennoxemea.com