Table 2-9     Electrical Specifications (PCI Expansion Unit)
Item
Number of power cords
Power cord length
Redundancy
Frequency
Maximum input current (*1)
Maximum power consumption
Apparent power
Rush current (*2)
Leakage current (*2)
*1 The current that flows through each power cord in a redundant configuration is half the value listed in
*2 The value is per power cord.
2.9.2

Power Cord Specifications

Table 2-10
and PCI expansion unit.
Table 2-10     Power Cords and Connector Shapes
Destination
Japan
North America
Europe
United Kingdom BS1363A
Italy
China
Taiwan
Korea
Denmark
Israel
India
South Africa
Argentina
Specification
Input Voltage of 100 to 120 VAC
2 (1 for each PSU)
Maximum length of 3.0 m (9.8 ft.)
1+1 redundant configuration
50 Hz/60 Hz, single phase
2.9 A
279 W
284 VA
40 A peak or less
1.75 mA
shows the power cords and the connector shapes for the SPARC M12-1
Power Cord Type
NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
CEE7/7
CEI 23-16/Ⅶ
GB2099
CNS10917
NEMA6-20
KSC8305 250V 10A
DEMKO 107
SI 32
IS1293
SABS 164
IRAM 2073
Chapter 2 Planning and Preparing for System Installation
Input Voltage of 200 to 240 VAC
2 (1 for each PSU)
Maximum length of 3.0 m (9.8 ft.)
1+1 redundant configuration
50 Hz/60 Hz, single phase
1.4 A
270 W
276 VA
40 A peak or less
1.75 mA
Table
2-9.
Connector Shape
IEC 60320-C13
29