Figure 2-4     Example of Service Areas for the SPARC M12-1 When Using a
Stepladder (Top View)
(*1)
1100 mm
(43.3 in.)
800 mm
(31.5 in.)
(*1)
140 0 mm
(55.1 in.)
*1 This area is required for using a stepladder, and it differs depending on the stepladder used. Referring to the
above figure, ensure that the service area is appropriate to the stepladder used. This area is required on either the
left or right side.
*2 To mount a chassis in the rack, an area with a depth of 1,200 mm (47.2 in.) is required in front of the rack.
If there is a possibility that a chassis will be added later, secure an area with a depth of 1,200 mm (47.2 in.) in front
of the rack.
Rear service area
Rack
(*1)
Front service area
(*2)
800 mm
900 mm
(31.5 in.)
(35.4 in.)
700 mm
(27.6 in.)
Chapter 2 Planning and Preparing for System Installation
Installation area
for stepladder
1100 mm
(43.3 in.)
(*1)
1400 mm
(55.1 in.)
800 mm
(31.5 in.)
105 0 mm
(41.3 in.)
140 0 mm
(55.1 in.)
17