Keypad Lock; Device Reset; Factory Reset; Hardware Reset - Johnson Controls KONOzw Operation Manualline

Table of Contents

Advertisement

Product Model: KONOzw
9.
K
L
EYPAD
OCK
KONOzw has provided the keypad lock function to limit full user-control. The function can be set either
through the device itself or by Z-Wave network.
There are only 1 level of keypad lock on the device
-
Level 1: Not available.
-
Level 2: When keypad lock is set to level 2, both the rotary and press button will have no function and
the device is not capable of leaving home screen.
To control the keypad lock at the device side:
Activate the Lock:
1. Press the knob so that backlight is illuminated and home screen is displayed
2. Press and Hold the knob for 10 seconds.
3. After 10 seconds device will enter keypad lock level 2.
4. The rotary control and press button will no longer operate, however the device can still be controlled
via the App or web portal.
Cancel the lock:
1. Press the knob so that backlight is illuminated and home screen is displayed
2. Press and Hold the knob for 10 seconds.
3. After 10 seconds device will unlock the keypad
To control the keypad lock / unlock via Z-Wave Command:
Command Class
Command
Protection
01 – Protection Set
10. D
R
EVICE
ESET
10.1

Factory Reset

Note:
Please use this procedure only when the network primary controller is missing or otherwise
inoperable.
1. Enter the installer setting menu and select the installer option #99, then press the knob to confirm.
2. All the device parameters will be restored to factory default. The Z-Wave network setting will also be
erased. User must perform the device inclusion with their hub / gateway again to re-establish the
network.
10.2

Hardware Reset

1. To reboot the device, remove the KONOzw front from the base. Locate the reset button directly above
the battery compartment, then press and hold for 3 seconds to reboot. Alternatively, remove the
power or battery completely and then power the device again activate the hard reset.
Operation Guideline
Value Definition
0x00 : No lockout (default)
0x01 : Reserved
0x02 : Level 2 lockout
Copyright  Johnson Controls Inc 2019 All Rights Reserved
Page 16 of 19