Ycas0543 - Ycas0623 - York MILLENNIUM YCAS Installation Operation & Maintenance

Air-cooled screw liquid chiller
Table of Contents

Advertisement

Technical Data
All dimensions
are in mm unless
otherwise noted.
(It is recommended that power
wiring enters on the right side.
If left entry is used, be sure
that space is available
for large wire bending radius.)
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high
pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control
center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m;
control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall
may be higher than the unit.
72
DIMENSIONS – YCAS0543 – YCAS0623
LD02991
LD02993