Electrical Data; Multiple Point Power Supply Connection - York MILLENNIUM YCAS Installation Operation & Maintenance

Air-cooled screw liquid chiller
Table of Contents

Advertisement

Technical Data
(Each of Two Field Provided Power Supply Circuits individually protected with Branch Circuit Protection.
Field Connections to Factory provided Terminal Block (Std), Disconnects (Opt), or Breakers (Opt) in each of the two Motor Control Centers.)
Model
Volts
Min. NF
YCAS
MCA
1
Disc. Sw.
2
0373
380
148
150
0403
380
160
200
0453
380
188
200
0503
380
215
250
0543
380
193
200
0573
380
227
250
0623
380
247
250
0653
380
232
250
* "Optional" Circuit Breakers are REQUIRED for units with CE mark.
See page 63 for Electrical Data Notes.
OPTIONAL SINGLE-POINT POWER SUPPLY WITH INTERNAL UNIT CIRCUIT BREAKERS
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in ‘Option Panel’.
Chiller
Model
Volts
Min. NF
YCAS
MCA
1
Disc Sw.
0373
380
296
0403
380
321
0453
380
375
0503
380
430
0543
380
387
0573
380
455
0623
380
493
0653
380
464
46

ELECTRICAL DATA

MULTIPLE POINT POWER SUPPLY CONNECTION

SYSTEM #1 FIELD SUPPLIED WIRING
Overcurrent
Factory Provided (Lugs) Wire Range
Protection
13
*Std. Terminal
Min.
3, 5
Max.
4, 6
Block
200
250
# 2 - 4/0
200
250
# 2 - 300
225
300
# 2 - 300
300
350
# 1 - 500
250
300
# 2 - 300
300
350
# 1 - 500
300
400
# 1 - 500
300
350
# 1 - 500
Internal Branch Circuit Protection (Breakers) per Compressor)
Field Provided Power Supply
Over-Current Protection
Min.
Max.
2
3, 5
400
300
350
400
350
400
400
400
450
600
450
500
400
400
450
600
500
500
600
500
600
600
500
500
7
*Opt. NF.
Opt. C.B.
Disc Sw.
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
(2) 3/0-250
# 6 AWG - 350
# 6 AWG - 350
# 6 AWG - 350
(2) 3/0-250
# 6 AWG - 350
(2) 3/0-250
# 6 AWG - 350
(2) 3/0-250
FIELD-SUPPLIED WIRING
Factory Provided (Lugs) Wire Range
13
Standard
Terminal Block
4, 6
# 1 - 500
(2) # 2 - 300
(2) # 2 - 300
(2) # 1 - 500
(2) # 2 - 300
(2) # 1 - 500
(2) # 1 - 500
(2) # 1 - 500
Compressor
Fans
11, 12
FLA
LRA
RLA Y-LRA
X-LRA Qty.
(Ea.) (Ea.)
108
241
761
3
4.4
17.1
118
241
761
3
4.4
17.1
140
309
979
3
4.4
17.1
161
309
979
3
4.4
17.1
141
309
979
4
4.4
17.1
168
309
979
4
4.4
17.1
183
309
979
4
4.4
17.1
168
309
979
5
4.4
17.1
7
Optional NF
Disc. Switch
(2) 3/0-250
(2) 3/0-250
(2) 3/0-250
(3) 2/0-400
(2) 3/0-250
(3) 2/0-400
(3) 2/0-400
(3) 2/0-400
YORK INTERNATIONAL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents