9.3

Servicing

Servicing involves activities and procedures for maintaining and restoring the operating
condition of the devices.
Required tools
The following tools are required for replacing components:
• Spanner or socket spanner (w/f 10)
• Spanner or socket spanner (w/f 13)
• Spanner or socket spanner (w/f 16/17)
• Spanner or socket spanner (w/f 18/19)
• Hexagon-socket spanner (size 8)
• Torque wrench up to 50 Nm
• Screwdriver size 1 / 2
• Screwdriver Torx T20
• Screwdriver Torx T30
Tightening torques for current-carrying parts
When securing connections for current-carrying parts (DC link, motor connections, busbars),
you must observe the following tightening torques.
Table 9-1
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
Tightening torques for connecting current-carrying parts
Screw
M6
M8
M10
M12
Maintenance and servicing
Torque
6 Nm
13 Nm
25 Nm
50 Nm
9.3 Servicing