Cooling circuit and coolant properties
8.4 Horizontal installation
Housing for air guidance
The fan(s) can suck the air out of the module only if air cannot be sucked in between the
module and the fan. A housing (enclosure) must therefore be provided between the fan and
the module.
Motor connection cover
The motor connection on a horizontally mounted module must be covered. This cover must
be perforated. The perforations should have an opening area of 8 x 30 mm with a perforation
spacing of 3 to 5 mm (Fig. 8-12).
Fig. 8-12
The following table lists the fans required for different module types and also specifies the
volumetric flow which must be provided through the SINAMICS device. The data must be
regarded as minimum values.
If the specified fan is not available, an alternative fan can be used provided that its
characteristic is higher than that of the minimum fan recommended. Data sheets for the
recommended minimum fan with characteristic are available on request from EBM-Papst.
Table 8-8
Volumetric flow requirement and number of fans needed for horizontal mounting
Type
Power Module FL, GL
Basic Line Module FBL, 740 A (400 V), 420 A (690 V)
Basic Line Module FBL, 1220 A (400 V), 730 A (690 V)
Basic Line Module GBL
Motor Module GXL
Motor Module HXL
Motor Module JXL
Available at info2@de.ebmpapst.com
*)
8-18
Example of protective cover for motor connection
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
Required
volumetric air flow
Papst 4114NXH or Papst 4114NHH or
[dm³/s]
Papst 4184NXH (120 x 120 mm)
15
27
44
63
15
25
63
Number of fans
1
1
2
2
1
1
2
Chassis Power Units Liquid Cooled
*)