Table 5-8
Technical specifications for the Motor Module, 675 V – 1080 V DC
Order number
Rated output current I
N
Base load current I
L
Base load current I
H
Max. output current I
max
kVA rating
1)
Power on basis of I
H
Rated DC link current
Connection voltages
- DC link voltage
- Electronics power supply
Output voltage
Rated pulse frequency
Max. pulse frequency without derating
Max. pulse frequency with derating
Electronics current drain (24 V DC)
Cooling type
DC link capacitance
Power loss
2)
- Air / Coolant
- Total losses
Max. coolant temperature:
- without derating
- with derating
Coolant requirement
3)
Liquid volume of integrated heat exchanger
Typ. pressure drop with volumetric flow
Sound pressure level
DC link/motor connection
Max. connection cross-section
DC link connection (DCP, DCN)
Motor connection (U2, V2, W2)
PE connection
Max. cable length
Degree of protection
Dimensions
Width
Height
Depth
Frame size
Weight
UL listed fuse
5)
Number (connected in parallel)
Rated current
Size acc. to DIN 43620-1
kVA rating refers to the rated motor power of a typical 6-pole motor supplied with 690 V.
1)
At rated pulse frequency
2)
This value applies to both coolant options, i.e. water and water / Antifrogen N mixture with 45 %
3)
Antifrogen N.
This value applies to the water coolant option; for other coolant types, see Chapter 8.
4)
In order to build a UL-approved system, it is absolutely essential to use the specified fuses.
5)
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
6SL3325–
1TG35-8AA0
A
575
A
560
A
514
A
840
kW
560
kW
450
A
702
V
DC
V
DC
V
ACeff
kHz
1.25
kHz
1.25
kHz
5
A
1.46
Liquid cooling with integrated aluminium heat exchanger
μF
9670
kW
0.15 / 5.45
kW
5.60
°C
45
°C
50
l/min
16
dm³
0.74
Pa
70000
4)
dB(A)
54
mm²
Busbar
mm²
4 x 240
mm²
2 x 240
m
IP00
mm
265
mm
984
mm
545
HXL
kg
110
3NE3 232-0B
2
400
1
5.6 Technical specifications
1TG38–1AA0
1TG41–0AA0
810
1025
790
1000
724
917
1185
1500
800
1000
710
900
990
1250
675 to 1080
24 (20.4 – 28.8)
0 to 0.72 x DC link voltage
1.25
1.25
1.25
1.25
5
5
1.46
1.46
14000
16000
0.45 / 9.11
0.50 / 10.37
9.56
10.87
45
45
50
50
27
27
1.56
1.56
70000
70000
56
56
Flange connection with screws M12
Busbar
Busbar
4 x 240
4 x 240
2 x 240
2 x 240
300 (shielded) / 450 (unshielded)
IP00
IP00
295
295
1496
1496
545
545
JXL
JXL
220
220
3NE3 335
3NE3 337-8
2
2
560
710
2
2
Motor Modules
1TG41–3AA0
1270
1230
1136
1845
1200
1000
1550
1.25
1.25
5
1.46
19330
0.56 / 12.92
13.48
45
50
27
1.56
70000
56
Busbar
4 x 240
2 x 240
IP00
295
1496
545
JXL
220
3NE3 340-8
2
900
2