Register
Number
201
202
203
206
12.4
Setup
Register
Number
3000
3200
3201
3401
3403
3600
3601
3602
12.5
Measured values
Register
Number
100
104
SITRANS LR110
Operating Instructions, 12/2020, A5E49829013
Register Name
Data type Configurable Values
Baud Rate
enum16
r/w
Parity
enum8
r/w
Stopbits
enum8
r/w
Delay Time
uint16
r/w
Register Name
Data type Configurable Values
Byte Oder (Floating
enum8
point format)
r/w
Distance unit
enum16
r/w
Temperature unit
enum16
r/w
Min.-Adjustment
float32
r/w
Max.-Adjustment
float32
r/w
Medium type
enum16
r/w
Application liquid
enum16
r/w
Application solid
enum16
r/w
Register Name
Data
type
Access
Status
enum8
ro
PV Unit
enum16
Technical data and dimensions
1200, 2400, 4800,
9600, 19200, 38400,
57600
0 = None, 1 = Odd, 2 =
Even
1 = None, 2 = Two
10 ... 250
0=ABCD, 1=CDAB,
2=DCBA, 3=BADC
44=ft, 45=m, 47=in,
49=mm
32=°C, 33=°F, 35=K
0 ... Measurement
range
0 ... Measurement
range
0=Liquids, 1=Solids
0 =Storage, 1= Process,
13=Wetwell, 8=Plastic,
9=Open, 12=Demo
0=Silo, 4= Bin/Hopper,
3=Open,12=Demo
Note
Bit 0: Invalid Measurement Value PV, Bit 1: Invalid
Measurement Value SV, Bit 2: Invalid Measurement
Value TV, Bit 3: Invalid Measurement Value QV
32=Degree Celsius, 33=Degree Fahrenheit,
39=Percent, 40=US Gallons, 41=Liters, 42=Imperial
12.4 Setup
Unit
Default
Value
–
9600
–
0
–
1
ms
50
Unit
Default
Value
–
0
-
m
-
°C
-
0
-
Measurement
range
-
Liquids
-
Storage
-
Silo
45