Standard Setup (St Setup) (3.2.) - Siemens SITRANS LR460 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR460:
Table of Contents

Advertisement

Parameter assignment
8.5 Input (3.)
8.5.2

Standard setup (ST SETUP) (3.2.)

Antenna (3.2.1.)
Identifies antenna configuration.
Options
Response rate (RESPRATE) (3.2.2.)
Sets the reaction speed of the device to measurement changes in the target range.
Related param-
eters
Values
Note
If you change Response Rate it resets the following parameters: LOE Timer, Fill Rate, and
Empty Rate.
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy and a smoother output signal: faster settings allow
for more level fluctuation.
For instructions on usage, see "LOE Timer" in Echo confidence (Page 134). For technical
1)
details, see "LOE timer" in Fail-safe (3.5.1.) (Page 83).
78
NO HORN
3 IN
4 IN
Response rate
LOE Timer
(minutes)
* SLOW
100
MED
10
FAST
1
Fill rate
1)
0.1 m/minute
1 m/minute
10 m/minute
Operating Instructions, 10/2021, A5E42035355-AB
Empty rate
0.1 m/minute
1 m/minute
10 m/minute
SITRANS LR460