Diagnostics and troubleshooting
9.3 Status messages according to NE 107
Fault rectification
The first measures are:
A smart device (smartphone/tablet) with the adjustment app or a PC/notebook
with the PDM and the suitable EDD offer you further comprehensive diagnostic
possibilities. In many cases, the causes can be determined in this way and the faults
eliminated.
Reaction after fault rectification
Depending on the reason for the fault and the measures taken, the steps described
in chapter " Setup" must be carried out again or must be checked for plausibility and
completeness.
9.3
Status messages according to NE 107
Failure
Code
Text message
F013
no measured value
available
F017
Adjustment span too
small
F025
Error in the
linearization table
F036
No operable software
F040
Error in the
electronics
F080
General software
error
28
Signal processing
Evaluation of fault messages
Checking the output signal
Treatment of measurement errors
Cause
No measured value in the switch-on
phase or during operation
Transmitter tilted
Adjustment not within specification
Index markers are not continuously
rising, for example illogical value pairs
Checksum error if software update
failed or aborted
Limit value exceeded in signal
processing
Hardware error
General software error
Rectification
Check or correct installation and/or
parameter settings
Clean the antenna system
Change adjustment according to the
limit values (difference between min.
and max. ≥ 10 mm)
Check linearization table
Delete table/Create new
Repeat software update
Send transmitter for repair
Restart transmitter
Send transmitter for repair
Restart transmitter
Operating Instructions, 12/2020, A5E49829013