Diagnosis Data, Device Information; Function Codes - Siemens SITRANS L Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Technical data and dimensions
12.7 Diagnosis data, device information
12.7

Diagnosis data, device information

Register
Number
2300
2307
2308
12.8

Function codes

The function codes (FCs) are automatically used by the Modbus master to carry out
certain actions such as reading or writing.
With this command, any number (1-127) of holding registers is read out. The start
register, from which the readout should start, and the number of registers are
transmitted.
Request:
Response:
With this command, any number (1-127) of input registers is read out. The start
register, from which the readout should start as well as the number of registers are
transmitted.
Request:
Response:
This function code is used to write to a single Holding Register.
Request:
Response:
48
Register Name
Type
Current
uint32
diagnostic code
ro
Device status
uint8
ro
Device serial
string
number
(12
characters)
Parameter
Function Code
Start Address
Number of Registers
Function Code
Byte count
Register Value
Parameter
Function Code
Start Address
Number of Registers
Function Code
Byte count
Register Value
Parameter
Function Code
Start Address
Number of Registers
Function Code
Note
According to NAMUR NE 107 recommendation
Current event category: 0 = ok, 1 = failure, 2 = check,
4 = maintenance, 8 = out of spec
-
Length
Code/Data
1 Byte
0x03
2 Bytes
0x0000 to 0xFFFF
2 Bytes
1 to 127 (0x7D)
1 Byte
0x03
1 Byte
2*N
N*2 Bytes
Data
Length
Code/Data
1 Byte
0x04
2 Bytes
0x0000 to 0xFFFF
N*2 Bytes
1 to 127 (0x7D)
1 Byte
0x04
1 Byte
2*N
N*2 Bytes
Data
Length
Code/Data
1 Byte
0x06
2 Bytes
0x0000 to 0xFFFF
2 Bytes
Data
1 Byte
0x04
Operating Instructions, 12/2020, A5E49829013