Installation

INSTALLING OPTIONAL SPRING ISOLATORS

To install these spring isolators, first remove the bolts
and nuts from the spring isolator bracket. Bolt the isola-
tor bracket to the unit foot support before the unit is
located on the floor. Place the four spring isolators in
FIG. 8 – SPRING ISOLATORS (OPTIONAL)
18
LD02946A
SPRING ISOLATORS (4 Per Unit) – ENGLISH
COMPRESSOR
SYSTEM OPERATING
SIZE
WEIGHT (Lbs.)
UP to 6,865
6,866 to 9,818
S0, S1,
9,819 to 12,182
S2, S3
12,183 to 15,272
15,273 to 18,272
18,273 to 22,909
UP to 22,909
S4, S5
22,910 to 26,044
26,045 to 32,101
SPRING ISOLATORS (4 Per Unit) – SI
COMPRESSOR
SYSTEM OPERATING
SIZE
WEIGHT (mm)
UP to 3,114
3,115 to 4,453
S0, S1,
4,454 to 5,525
S2, S3
5,526 to 6,927
6,928 to 8,288
8,289 to 10,392
UP to 10,392
S4, S5
10,392 to 11,813
11,814 to 14,561
position in accordance with the product drawing, Form
160.47-PA1. The threaded adjusting bolts in each isola-
tor should be screwed out of the isolator until the ex-
tended head of the screw fits snugly into the isolator
bracket hole. Then the unit is lowered over the adjust-
ing bolts. Refer to Figure 8.
PART NO.
029-18479-001
029-18479-002
029-18479-003
029-18479-004
029-18480-001
029-18480-002
029-18480-002
029-18480-003
029-18480-004
PART NO.
029-18479-001
029-18479-002
029-18479-003
029-18479-004
029-18480-001
029-18480-002
029-18480-002
029-18480-003
029-18480-004
LD02947A
YORK INTERNATIONAL