VIBRATION ANALYSIS

Vibration analysis performed at regular intervals is a
useful diagnostic tool that can detect internal damage to
rotating machinery and component parts. This service
should be performed by a skilled technician trained in
the use and operation of the equipment. Fig. 26 is pro-
vided to properly locate the transducer measurement
SPECTRAL ALARM BANDS FOR 4/6 LOBE TWIN SCREW CHILLERS
(YS___S0 through S5 YORK Screw Chillers)
MALE
INLET
FEMALE
INLET
FIG. 26 – TRANSDUCER MEASUREMENT POINTS
YORK INTERNATIONAL
MALE
OUTLET
COMPRESSOR
(BOTTOM)
FEMALE
OUTLET
points. Locating the transducers at these locations will
enable the data to be analyzed against a large database
of sound and vibration data.
Note the natural or pumping frequency of the York YS
compressor is 238 HZ at 60 HZ and 198 HZ at 50 HZ.