Pn-X2 - Siemens SIMATIC HMI Unified Comfort MTP700 Operating Instructions Manual

Hide thumbs Also See for SIMATIC HMI Unified Comfort MTP700:
Table of Contents

Advertisement

Ethernet parameters Port 1, Ethernet Parameters Port 2
● "Activate this port for use": Option to activate or deactivate the X1P1 or X1P2 ports. The
default setting is "Activated".
● "Mode and speed": List for selecting the transmission type and transmission rate for the
interface; selection options: "Automatic" (default setting) or "100Mbps / FDX" (100 Mbps,
full-duplex). Use the default setting "Automatic" preferably.
● "Boundaries":
– "End of detection of accessible nodes": DCP frames for detecting accessible nodes
– "End of topology discovery": LLDP frames for topology discovery are not forwarded.
Changes under "Ethernet parameters Port 1" and "Ethernet parameters Port 2" require a
restart, the "PROFINET Port Settings" dialog box is displayed. Restart the system using the
"Restart" button.
5.5.1.3

PN-X2

Under "PN-X2" you define the parameters for the X2 interface.
PROFINET
● "Device name": Display field with the PROFINET name of the HMI device that was
defined in the settings under "PN-X1".
● "Converted name": Display field with the PROFINET name of the HMI device, contains
the entry under "Device name", automatically converted according to PROFINET naming
conventions.
● "MAC address": Display field with the MAC address of X2 interface of the HMI device.
Unified Comfort Panels
Operating Instructions, 03/2020, A5E46641217-AA
are not forwarded. Nodes located beyond this interface are no longer accessible.
Operating the Control Panel
5.5 Network and Internet
89