3 SPECIFICATIONS
3.5.44 Mode setting of Alert 1 to 4
(buffer memory address 192 to 195, 208 to 211: Un\G192 to Un\G195, Un\G208 to
Un\G211)
3.5.45 Scaling value (buffer memory address 196, 212: Un\G196, Un\G212)
3 - 82
This setting is available in the setting mode only.
For confirming the change, it is necessary to turn on the setting change command
(YnB).
(1) Sets the alert mode which gives an alarm.
(2) The alert values of alert alarms 1 to 4 are set to the following buffer memory
addresses.
• Channel 1: 38 to 41
• Channel 2: 70 to 73
(3) The correspondences between buffer memory addresses and channels are
listed below.
Mode setting item
Alert 1
Alert 2
Alert 3
Alert 4
(4) The following table indicates the alert modes and set values.
Refer to Section 3.2.10 for the alert functions of the Q62HLC.
Alert mode
Setting
Upper limit input alert
1
Lower limit input alert
2
Upper limit deviation
3
alert
Lower limit deviation
4
alert
Upper/lower limit
5
deviation alert
Within-range alert
6
(5) The alert function is not executed with the default value "0"
(1) The value which scaled the measured value (PV) is stored.
(2) The scaling method differs depending on thermocouple input or micro
voltage/voltage/current input.
For details of the scaling function, refer to Section 3.2.14.
CH1
CH2
192
208
193
209
194
210
195
211
Alert mode
Upper limit input alert with
wait
Lower limit input alert with
wait
Upper limit deviation alert
with wait
Lower limit deviation alert
with wait
Upper/lower limit deviation
alert with wait
—
MELSEC-Q
Alert mode
Setting
7
—
8
—
Upper limit deviation alert
9
with re-wait
Lower limit deviation alert
10
with re-wait
Upper/lower limit deviation
11
alert with re-wait
—
—
Setting
—
—
12
13
14
—
3 - 82