3 SPECIFICATIONS
3.5.19 AT differential gap (buffer memory address 46, 78: Un\G46, Un\G78)
3.5.20 AT additional lag (buffer memory address 47, 79: Un\G47, Un\G79)
3 - 70
(1) Set the waiting time needed for next switching of output ON/OFF status from the
previous switching at auto tuning.
(2) The setting range is 0 to 10000 (0.00 to 100.00s).
(3) The target of setting value for standard mode is 10 (0.1s), for fast response
mode is 1 (0.01s).
Measured value
Set value (SV)
Output
(1) Set the waiting time for switching the output ON/OFF status after the measured
value (PV) has passed the set value (SV) at auto tuning.
(2) The setting range is 0 to 1000 (0.00 to 10.00s).
(3) The target of setting value for standard mode is 10 (0.1s), for fast response
mode is 1 (0.01s).
Measured value
Set value (SV)
Output
Measured
value (PV)
AT difference gap
Measured value
(PV)
AT additional lag
MELSEC-Q
Time
Time
3 - 70