Converter terminals

Table 4- 2
Connection, cross-section and tightening torque for PM240P-2 Power Modules
Converter
FSD
Line supply,
motor
FSE
FSF
Line supply,
motor
Procedure
Proceed as follows to establish the connections:
1. Ensure that the device is in a no-voltage condition and the DC link is discharged.
2. Establish the connections as described in the following sections.
This means that you have established the connections.
Connections, frame sizes FSD ... FSF
You must remove the covers from the connections in order to connect the line supply and
motor cables to the converter.
Figure 4-4
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
Connection
Screw-type termi-
10 ... 35 mm
nal
25 ... 70 mm
35 ... 2 × 120 mm
22 ... 25 Nm
Cable lug accord-
ing to SN71322
Remove the connection covers
4.2 Connecting the line and motor cable at the converter
Cross-section, tightening torque
Metric
, 2.5 ... 4.5 Nm
20 ... 10 AWG, 22 lbf in
2
8 ... 2 AWG, 40 lbf in
, 8 ... 10 Nm
6 ... 3/0 AWG, 88.5 lbf in
2
,
1 ... 2 × 4/0 AWG, 210 lbf in --
2
Connecting
Stripped
insulation
Imperial
length
18 mm
25 mm
43