Siemens SINAMICS G120 PM240P-2 Installation Manual page 18

Frequency converters
Table of Contents

Advertisement

Introduction
Component specification according to UL
The components of the SINAMICS G120 product family are UL-certified. The certification is
indicated on the products using the UL Listing Mark.
If the converter is protected using semiconductor fuses, then the fuses must be installed in
the same electrical cabinet as the converter itself.
You can find proof of the certification on the Internet UL certificates (http://www.ul.com)
under "Tools / Online Certifications Directory" by entering the file number or the "Name".
The UL file number for the Power Modules of the SINAMICS G120 product family is:
● E192450 for FSD, FSE and FSF
Permissible motors
Note
Motors for converter operation
Only use motors that are suitable for operation with converters with a DC link.
Motors for 400 V Power Modules
For the 400 V Power Modules, induction motors are permissible in the range from
25 % ... 150 % of the converter power without any restrictions.
Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% ... 150 % of the converter power without any restrictions.
Continuous development within the scope of product maintenance
Converter components are being continuously developed within the scope of product
maintenance. Product maintenance includes, for example, measures to increase the
ruggedness or hardware changes which become necessary as components are
discontinued.
These further developments are "spare parts-compatible" and do not change the article
number.
In the scope of such spare parts-compatible ongoing development, plug connector or
connection positions are sometimes slightly modified. This does not cause any problems
when the components are properly used. Please take this fact into consideration in special
installation situations (e.g. allow sufficient reserve regarding the cable length).
16
Hardware Installation Manual, 06/2020, A5E37800827C AD
Power Module PM240P-2

Advertisement

Table of Contents
loading

Table of Contents