Installing
3.2 EMC-compliant installation of a machine or system
3.2.3
Electromechanical components
Surge voltage protection circuit
● Connect surge voltage protection circuits to the following components:
– Coils of contactors
– Relays
– Solenoid valves
– Motor holding brakes
● Connect the surge voltage protection circuit directly at the coil.
● Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.
24
Hardware Installation Manual, 06/2020, A5E37800827C AD
Power Module PM240P-2