Converters; General Data, 690 V Converters - Siemens SINAMICS G120 PM240P-2 Installation Manual

Frequency converters
Table of Contents

Advertisement

6.5
690 V converters
6.5.1

General data, 690 V converters

Property
Line voltage
Line system configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac-
cording to EN 61800-5-1
Pulse frequency
Short-circuit current rating
(SCCR) and branch protec-
tion
Braking methods
Degree of protection ac-
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection according
to EN 50274
Cooling in compliance with
EN 60146
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
Version
3 AC 500 V ... 690 V ± 10% (in operation -20% < 1 min)
with Class J fuses, maximum 600 V
Grounded TN/TT line systems or non-grounded IT line systems
Uk < 4%, line reactor is not required
> 0.9
3 AC 0 V ... 0.95 × input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the converter reduces the maximum output current.
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking
IP20; must be installed in a control cabinet
The converters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
Technical data
6.5 690 V converters
63