Drive (Gas Heat) Downflow - York SUNLINE MAGNADRY WR240 Technical Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNADRY WR240:
Table of Contents

Advertisement

262292-YTG-B-0107
TABLE 16: WR240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (GAS HEAT) DOWNFLOW
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
0.4
9892 1106 8.30 10.13 9366 1071 7.31 8.92 9127 1036 6.78 8.28 8665 1002
0.6
9526 1107 7.83 9.55 8976 1073 7.12 8.69 8723 1038 6.38 7.79 8257 1003
0.8
9158 1108 7.56 9.23 8600 1074 6.83 8.33 8333 1039 6.11 7.46 7820 1005
1.0
8796 1109 7.16 8.74 8222 1076 6.41 7.82 7927 1040 5.73 7.00 7424 1006
1.2
8418 1110 6.88 8.40 7817 1077 5.91 7.21 7490 1041 5.37 6.56 6981 1007
1.4
8033 1112 6.35 7.75 7420 1078 5.62 6.86 7074 1043 5.10 6.22 6505 1008
1.6
7639 1113 6.01 7.34 6944 1079 5.37 6.55 6594 1044 4.65 5.68
1.8
7167 1115 5.89 7.19
1 turn
10 HP motor
11000
10000
1 Turn
2 Turns
3 Turns
9000
4 Turns
5 Turns
8000
6 Turns
7000
6000
5000
0.2
Unitary Products Group
Blower Performance (Downflow Discharge)
-
-
-
-
-
-
2 turns
3 turns
7.5 HP motor
20-Ton Standard Drive, Gas Heat, Bottom Connection
0.4
0.6
0.8
KW
5.97
5.65
5.30
5.01
4.70
4.26
-
-
-
-
-
-
-
-
4 turns
VP68 x BK100
1.0
1.2
1.4
External Static ("WC)
BHP CFM RPM
KW
BHP CFM RPM
7.28 8311
968
5.34
6.52 8102
6.90 7887
969
5.01
6.12 7649
6.47 7469
970
4.73
5.77 7193
6.12 7051
971
4.52
5.51 6721
5.74 6604
972
4.19
5.12 6162
5.20
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5 turns
1.6
1.8
2.0
KW
BHP
932
4.91
5.99
934
4.54
5.55
935
4.12
5.03
936
3.95
4.83
937
3.56
4.35
-
-
-
-
-
-
-
-
-
-
-
-
6 turns
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnadry wr300Sunline magnadry wr180

Table of Contents