Wr Electrical Data - High Static Drive Motor W/O Powered Conv. Outlet - York SUNLINE MAGNADRY WR240 Technical Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNADRY WR240:
Table of Contents

Advertisement

TABLE 27: WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET
MODEL
VOLTAGE
(TONNAGE)
208
230
180
(15)
460
575
208
230
240
(20)
460
575
208
230
300
(25)
460
575
NOTE 1: HACR Type per NEC.
VOLTAGE LIMITATIONS
POWER SUPPLY
VOLTAGE
208/230-3-60
1
460-3-60
LIMITATIONS
575-3-60
1. Utilization Range "A" in accordance with ARI Standard 110.
40
COMPRESSORS
OD FAN
MOTORS
RLA
LRA
FLA EACH
EACH
EACH
22.4
164
2.1
22.4
164
2.1
10.9
100
1.2
8.3
78
0.9
30.1
225
2.4
30.1
225
2.4
15.5
114
0.9
12.1
80
0.6
42.3
245
2.4
42.3
245
2.4
17.6
125
0.9
14.5
100
0.6
VOLTAGE
MIN.
MAX.
187
414
518
ID
CONV
BLOWER
OUTLET
MOTOR
MODEL
AMPS
FLA
None
E18
20.0
0.0
E36
E54
E72
None
E18
20.0
0.0
E36
E54
E72
None
E18
10.0
0.0
E36
E54
E72
None
E18
7.5
0.0
E36
E54
E72
None
E18
38.6
0.0
E36
E54
E72
None
E18
38.6
0.0
E36
E54
E72
None
E18
19.3
0.0
E36
E54
E72
None
E18
16.2
0.0
E36
E54
E72
None
E18
38.6
0.0
E36
E54
E72
None
E18
38.6
0.0
E36
E54
E72
None
E18
19.3
0.0
E36
E54
E72
None
E18
16.2
0.0
E36
E54
E72
NOMINAL VOLTAGE
208
253
240
506
480
630
600
HEATER OPTION
KW
STAGES
AMPS
-
-
-
13.5
1
37.5
27
2
74.9
40.6
2
112.7
54.1
2
150.2
-
-
-
18.0
1
43.3
36.0
2
86.6
54.0
2
129.9
72.0
2
173.2
-
-
-
18.0
1
21.7
36.0
2
43.3
54.0
2
65.0
72.0
2
86.6
-
-
-
18.0
1
17.3
36.0
2
34.6
54.0
2
52.0
72.0
2
69.3
-
-
-
13.5
1
37.5
27
2
74.9
40.6
2
112.7
54.1
2
150.2
-
-
-
18.0
1
43.3
36.0
2
86.6
54.0
2
129.9
72.0
2
173.2
-
-
-
18.0
1
21.7
36.0
2
43.3
54.0
2
65.0
72.0
2
86.6
-
-
-
18.0
1
17.3
36.0
2
34.6
54.0
2
52.0
72.0
2
69.3
-
-
-
13.5
1
37.5
27
2
74.9
40.6
2
112.7
54.1
2
150.2
-
-
-
18.0
1
43.3
36.0
2
86.6
54.0
2
129.9
72.0
2
173.2
-
-
-
18.0
1
21.7
36.0
2
43.3
54.0
2
65.0
72.0
2
86.6
-
-
-
18.0
1
17.3
36.0
2
34.6
54.0
2
52.0
72.0
2
69.3
ELECTRIC HEAT CORRECTION FACTORS
VOLTAGE
208
230
460
575
262292-YTG-B-0107
MIN.
MAX. FUSE/
1
CIRCUIT
BRKR
AMPACITY
SIZE
(AMPS)
(AMPS)
78.8
100
78.8
100
118.7
125
165.9
175
175.2
200
78.8
100
79.1
100
133.3
150
154.9
175
198.2
225
39.3
50
39.6
50
66.6
70
77.5
90
99.1
110
29.8
35
31.0
35
52.7
60
61.3
70
78.7
90
118.1
150
118.1
150
141.9
150
189.1
200
198.4
225
118.1
150
118.1
150
156.5
175
178.2
200
221.5
250
58.7
70
58.7
70
78.3
80
89.1
100
110.7
125
46.9
60
46.9
60
63.6
70
72.2
80
89.5
100
143.4
175
143.4
175
143.4
175
189.1
200
198.4
225
143.4
175
143.4
175
156.5
175
178.2
200
221.5
250
62.9
80
62.9
80
78.3
80
89.1
100
110.7
125
51.7
60
51.7
60
63.6
70
72.2
80
89.5
100
kW CAP. MULTIPLIER
1.00
0.92
0.92
0.92
Unitary Products Group

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnadry wr300Sunline magnadry wr180