Siemens SITRANS F Series Operating Instructions Manual page 157

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Param‐
Meter
Display
eter ID
version
view
811
Advanced
-
812
Advanced
-
813
Advanced
-
814
Advanced
-
815
Advanced
-
816
Advanced
-
817
Advanced
-
818
Advanced
-
819
Advanced
-
820
Advanced
-
821
Advanced
St1
822
Advanced
St1
SITRANS FM MAG 8000
Operating Instructions, 03/2020, A5E03071515-AH
Parameter/data type
Leakage source
Start period for leakage
detection
Duration leakage detec‐
tion
Leakage value unit
Leakage limit
- Leakage excitation fre‐
quency
Leakage status
Periods with possible
leakage
Leakage periods before
alarm
Reset leakage period in‐
formation
Latest leakage period
flowrate
Latest leakage period vol‐
ume
Factory settings
Fixed parameter or meter data that are not changeable
Flow rate
120 min = 2:00 [24:00]
0
Flow / volume unit
1
1.5625 Hz
No faults
30
No
0
0
Parameter lists
F.8 800-899
Data range
Flow rate / volume
0 to 1440 detection minutes (0 to
23:50)
0 to 144 (10 to 1440 minutes)
The unit is updated once param‐
eter 811 change is downloaded
to the device and afterwards up‐
loaded to the pc
0 to 1x10
9
The unit is updated once param‐
eter 811 change is downloaded
to device and afterwards uploa‐
ded to pc
1/60 Hz, 1/30 Hz, 1/15 Hz,
1/5 Hz, 1.5625 Hz, 3.125 Hz,
6.25 Hz
Leakage status:
1: Finished successfully
2: Leakage detection running
3: Leakage detection failed (Sys‐
temStatus have fatal error)
4: Leakage detection failed
(Empty-pipe detection disabled)
5: Leakage detection failed (Coil
current off)
6: Leakage detection failed (In‐
sulation test was active during
detection)
7: Leakage detection stopped
because leakage parameter
was changed.
If none of the above-mentioned
leakage status messages is
pending, the message is "No
faults"
0 to 255
Yes / No
Value is reset to "No" when up‐
loading device parameters to pc
after command execution
157