Installer/Configuration Menu - White Rodgers 1F80-0224 Installation And Operating Instructions Manual

Blue 2" single stage thermostat 24-hour programmable
Table of Contents

Advertisement

INSTALLER/CONFIGURATION MENU

The confi guration menu allows you to set certain thermostat operating characteristics to your system or personal requirements.
To enter the menu: Set your thermostat to OFF and press the
fi rst item in the confi guration menu. Press RUN/HOLD to change to the next menu item or press TIME to go backwards to the
previous item in the menu. To exit the menu and return to the program operation, press PRGM. If no keys are pressed within
fi fteen minutes, the thermostat will revert to normal operation.
Menu
Press
Reference
Key
Number
1
and
2
RUN/HOLD*
RUN/HOLD*
3
RUN/HOLD*
4
RUN/HOLD*
5
RUN/HOLD*
6
RUN/HOLD*
7
RUN/HOLD*
8
RUN/HOLD*
9
RUN/HOLD*
10
RUN/HOLD*
RUN/HOLD*
11
RUN/HOLD*
*Press RUN/HOLD to advance to next item or TIME to move backwards to previous item
1) System Confi guration - Selects SS (Single Stage) or HP
(Heat Pump) operating mode. Default confi guration is SS.
For Heat Pump operation choose HP.
2) Select CS (Cool Savings™) - With Cool Savings™
enabled, the thermostat will make small adjustments to
the Setpoint temperature during periods of high demand
to reduce cooling system running time and save energy.
When the cooling system has been running for more than
20 minutes, humidity in the home will be lower and a higher
setpoint temperature will feel comfortable. After 20 minutes
of run time, the thermostat will start increasing the setpoint
temperature in steps of less than one degree as the system
continues to run. These adjustments will eventually cause
the system to satisfy the thermostat and turn the system off
to reduce the energy consumption. When the Cool Savings
feature is active and making adjustments, the display will
show "Save". The amount of the adjustments to the setpoint
temperature is dependent on the Cool Savings value that
is set, 1 being the least adjustment and 6 being the most
adjustment. With this feature set to OFF, no change will
Confi guration Menu
Displayed
Press
(Factory
to select from
Default)
listed options
SS
HP
CS
On
(OFF)
CS
1, 2, 3, 4, 5, 6
(3)
E
OFF
(On)
CR Heat
FA, SL
(ME)
CR Cool
SL
(FA)
CL
On
(OFF)
L
OFF
(On)
Temp
4 LO to
(0 HI)
4 HI
o
F
o
C
Change Filter
On
(OFF)
Change Filter
25 to 1975
(200 h)
and
buttons simultaneously. The display will show the
or
Select Single Stage (SS) or
Heat Pump (HP, 1 compressor)
Select Cool Savings Feature On or OFF
If CS selected On, selects Cool Savings value
Select Energy Management Recovery On or OFF
Select Adjustable Anticipation, cycle rate,
Heat Single Stage
Select Adjustable Anticipation, cycle rate,
Cool Single Stage
Select Compressor lockout OFF or On
Select Display Light On or OFF
Select temperature display adjustment higher or
lower
Select
o
F /
o
C Display (temperature units in Fahren-
heit or Celsius)
Select fi lter replacement indicator OFF or On
If Change Filter selected On, selects time interval for
Change Filter Indicator. (in 25 hour increments)
Returns to normal operation
occur when the cooling system is continuously running
during the periods of high demand. Periods of high demand
will normally occur during the late afternoon and early
evening on the hottest days of the summer.
3) Select
Energy
Management
Management Recovery (E) On enables the thermostat
to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start 5 minutes early for every 1° of
temperature required to reach setpoint.
4 & 5) Select Cycle Rate Selection - The factory default
setting for Single Stage Heat is Medium Cycle (ME). For
Single Stage Cool the default setting is fast (FA). To change
cycle rate, press the
The cycle rate differentials for different settings are:
MODE
Fast
(FA)
SS Heat
0.6°F
SS Cool
1.2°F
5
Comments
Recovery
-
Energy
and
buttons.
Medium
Slow
(ME)
(SL)
0.8°F
1.2°F
-
1.7°F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents