Service

The furnace DDC controller has diagnostic information for
troubleshooting the furnace operation. Reference VB1285 and
VB1287 documentation below as applicable.

Maintenance

Installation and maintenance must be performed only by qualified personnel
who are trained and experienced with this type of equipment and familiar
with local codes and regulations.
Improper installation, adjustment, alteration, service, or maintenance can
cause severe personal injury or death. Read and understand this installation
and maintenance manual thoroughly before installing or servicing this
equipment.
Electrical shock and moving machinery hazard.
LOCKOUT/TAGOUT all power sources prior to servicing the equipment.
Electrical shock can cause injury, death, and property damage. More than
one disconnect may be required to de-energize unit. All start-up and service
work must performed only by trained, experience technicians familiar with
this type of equipment. Read and follow the MicroTech controller manual
before operating or servicing. Bond the eqipment frame to the building's
electrical ground through the grounding terminalor other approved means.
Hot surface hazard.
May cause minor to moderate personal injury. Allow burner assembly and
chimney flues to cool before servicing equipment.
Prevent snow levels from blocking airflow into the furnace vestibule and
combustion air inlet. Ensure snow does not accumulate and interfere with
the operation of electronics within the vestibule.
www.DaikinApplied.com
WARNING
WARNING
WARNING
CAUTION
CAUTION
Planned maintenance is the best way to avoid unnecessary
expense and inconvenience. Inspect the heating system
at regular intervals by a trained and experienced service
technician. The following service intervals are typical for
average situations but should be adjusted per site conditions.
Fuel pressure and control settings should be made only by
trained and qualified personnel.
Always replace covers on burner controls and boxes as the
electrical contacts. Perform maintenance of controls, gas
valves, and other components in accordance with the furnace
module instruction manual.
Monthly
Check cabinet air filters and replace if dirty. After heavy
snowfall verify that combustion air intakes are not blocked by
snow. Periodically check during periods of snow accumulation
as drifting may also lead to combustion air intake blockage.
Twice Yearly
1. Combustion Air: Check combustion inducer fan for dirt
buildup and lint. Check combustion air intake louvers and
flue box/vent for accumulation of dirt and debris.
2. Cleaning: Inspect and clean flue tubes and combustion
chamber. Keep burner vestibule clean. Dirt and debris
can result in poor combustion and lower efficiency.
Yearly
1. Debris: Check vent terminal screens for blockages and
accumulation.
2. Heater and the Venting System: Shall be inspected
once a year by a qualified service agency.
3. Gas Train: Check all valves, piping and connections for
leakage with a rich soap solution or UL 913 combustible
gas leak detector. Any bubbling is considered a leak and
must be eliminated. Inspect and clean flame rod, ignition
electrode, and burner manifold.
4. Condensate Pan and Drain: Remove any debris that
may have accumulated in the drain pain and drain.
97
Unit Maintenance
IM 1287 • REBEL APPLIED ROOFTOP