Daikin Rebel Applied DPSA Installation And Start-Up Manual page 59

Packaged rooftop heating and cooling 30 to 52 tons r-410a refrigerant
Hide thumbs Also See for Rebel Applied DPSA:
Table of Contents

Advertisement

Econo Set-Up
OA Damper Set-Up
Control Temp= XXX°F
Vent Limit= 20%
Occ Clg Spt= 72.0°F
LoFlo V Lmt= 30%
Occ Clg DB= 2.0°F
DCV Limit= 10%
Disch Air= XXX.X°F
OAD Position= XXX%
UseDATClgSpt=Yes
Min OA Pos= XXX%
DAT Econ Spt= 55.0°F
Min OA Src= ___________
DAT Econ DB= 2.0°F
Min OA Reset= None
External Reset
Clg Stage Time= 5min
Econ Chgovr= EnthOAT
OA @ MinV/mA= 0%
OA Temp= XXX°F
OA @ MaxV/mA= 100%
Chgover Temp= 70.0°F
Min V/mA= 0.0V
Econo Dif f= 2°F
Max V/mA=10.0V
Econo FDD= On
CO2 Reset
Econo Reset= None
CO2 Reset= Yes
Min Econ Spt= 55.0°F
PPM@DCVLmt= 800PPM
Min Econ Spt @= 0
PPM@VntLmt= 1000PPM
Max Econ Spt= 65.0°F
CO2 PPM = XXXXppm
Max Econ Spt @= 100
CO2 QMXSnsr =QMX1
Max OAT Lmt @= 75°F
Flow Reset
Min OAT Lmt @= 70°F
OA Flow Reset= Yes
Calibrate OAD=No
OA Flow= XXXXXCFM
Pos Sw Open= 97%
OA Flow Spt= 2000CFM
Max Sw Diff= 3%
OA Flow DB= 3%
Pos Sw Close= 3%
BSP Reset
Min Sw Diff= 5%
BSP OA Ovrd= No
OAD Sw Status=_________
BldgSP Spt= 0.05in
OAEOffset= 0.0°F
BSP DB= 0.010in
OADewpoint=___________
OARelHum=____________
OAEnthalpy=___________
RADewpoint=___________
RARelHum=____________
RAEnthalpy=____________
DATSptEnth=___________
www.DaikinApplied.com
Heating Set-Up
Control Temp= XXX°F
Occ Htg Spt= 68.0°F
Occ Hlg DB= 2.0°F
Disch Air= XXX.X°F
DAT Htg Spt= 85.0°F
DAT Htg DB= 2.0°F
EffSpactT= XXX°F
Unocc Clg Spt= 85.0°F
Unocc Dif f= 3.0°F
Htg Stage Time= 5min
OA Temp= XXX.X°F
Htg Hi OAT Lk= 55°F
OAT Diff= 2°F
Htg Reset= None
Min Htg Spt= 55.0°F
Min Htg Spt @= 0
Max Htg Spt= 120.0°F
Max Htg Spt @= 100
Min DAT Ctrl= Yes
Min DAT Limit= 55.0°F
MWU Sensor= CtrlTemp
StgGpriState= ____
StgGSpltState= ____
StgGDiagCode= ____
ModGState= ____
ModGDiagCode= ____
ModGErrCode= ____
F&BP Method= OpenVlv
F&BP ChgOvrT= 37°F
Dehum Set-Up
Dehum Method= None
RelHum 1=XXX%
RelHum 2=XXX%
Hum 1 Spt=50%
Hum 2 Spt=50%
Dewpoint 1=XXX°F
Dewpoint 2=XXX°F
Dewpnt 1 Spt=XXX°F
Dewpnt 2 Spt=XXX°F
Rel Hum DB = 2%
Dewpoint DB= 2°F
LCT Setpoint= XXX°F
LCT Spt Reset= None
Min LCT Spt= 45°F
Min LCT Spt@= 0.0
Max LCT Spt= 52.0°F
Max LCT Spt@= 100
Min Rheat Spt= 55.0°F
Max Rheat Spt= 65.0°F
DAT Clg DB= 2.0°F
DAT Htg DB= 2.0°F
Unocc Dehum= No
59
Unit Operation
Humidity Sensor Set-Up
Hum Sensor 1= SpaceH1
Hum Sensor 2 = OAH
SpcHumSensType = VDC
SpcHum MinSig= 0.0V
SpcHum MaxSig= 10.0V
SpaceRel Hum 1= __________
SpaceDwpnt1= ____________
SpaceRel Hum2= __________
SpaceDwpnt2= ____________
RARelHum= ______________
RADewpoint= _____________
OARelHum= ______________
OADewpoint= _____________
Energy Rec Set-Up
Energy Rcvy= Yes
ER Wheel= ____________
Wheel Cap= XXX%
Whl Spd Cmd= XXX%
ERWhlRotSw= __________
ER1ErrStatus= __________
ER2ErrStatus= __________
ER LWT= XXX°F
ER EWT= XXX°F
RARelHum=XXX%
Relief Damper Set-Up
Exh Plen Press=X.XXXin
Ef fExh PSP Spt= _____
Rel Dmpr Cmd= _____
ExhPSP Lo Spt= 0.150in
ExhPSP Hi Spt= 0.350in
Exh PSP DB= 0.050in
Space Sensor Set-Up
CommissionSnsrs= No
Sensor1SN= 000000
Sensor2SN= 000000
Sensor3SN= 000000
SerialNo1= _____________
SerialNo2= _____________
SerialNo3= _____________
IM 1287 • REBEL APPLIED ROOFTOP
Configurable I/O
Apply IO Chgs= No
X1 Cfg= AI_V
Input X1=_______________
X2 Cfg= AI_V
Input X2= ______________
X3 Cfg= AI_V
Input X3=_______________
X4 Cfg= AI_V
Input X4= ______________
X5 Cfg= AI_V
Input X5=_______________
X6 Cfg= AI_V
Input X6= ______________
X7 Cfg= AI_V
Input X7=_______________
X8 Cfg= AI_V
Input X8= ______________
Alarm/Event Config
Alarm Limits
Hi Disch Temp= 170°F
Lo Disch Temp= 40°F
Hi Return Temp= 120°F
Alarm Out Config
Faults= Fast
Problems= Slow
Warnings= Off