Rebel Applied units operate with 115V and 24V control circuit
power. All field control wiring connections are made at the class
II terminal block TBLV2 which is located in the Low Voltage
Control Panel, shown in
Figure 40
NOTE: The installation of all field wiring, must comply with all
applicable local codes and ordinances. The warranty
may be limited or certain aspects excluded if the field
wiring is not in accordance with these standards.
If a single conduit containing 24V and 115V wiring is
run above the roofline between units, consider the
24V wiring within as an NEC Class I wiring system.
Figure 42: Wiring Raceway, Air Handler Sections
Figure 43: Wiring Connections Control Box (located in Condenser Section, Shown without Doors or Panels)
Wiring entrance point from air
www.DaikinApplied.com
Wiring raceway (remove cover for access to
harnesses from main control box to unit-
mounted control devices)
handler sec�on
Wiring entrance point for
condenser fan wires
Wiring entrance point
to main control box
from outside of unit
35
Unit Wiring
Wiring entrance
point to low
voltage control box
IM 1287 • REBEL APPLIED ROOFTOP