Navigation Mode; Edit Mode; Smoke And Fire Protection - Daikin Rebel Applied DPSA Installation And Start-Up Manual

Packaged rooftop heating and cooling 30 to 52 tons r-410a refrigerant
Hide thumbs Also See for Rebel Applied DPSA:
Table of Contents

Advertisement

Navigation Mode

In the Navigation Mode, when a line on a page contains no
editable fields all but the value field of that line is highlighted
meaning the text is white with a black box around it. When the
line contains an editable value field the entire line is inverted
when the cursor is pointing to that line.
When the navigation wheel is turned clockwise, the cursor
moves to the next line (down) on the page. When the wheel is
turned counter-clockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the
cursor moves.
When the Back Button is pressed the display reverts back to
the previously displayed page. If the Back button is repeated
pressed the display continues to revert one page back along
the current navigation path until the "main menu" is reached.
When the Menu (Home) Button is pressed the display reverts
to the "main page."
When the Alarm Button is depressed, the Alarm Lists menu is
displayed.

Edit Mode

The Editing Mode is entered by pressing the navigation wheel
while the cursor is pointing to a line containing an editable field.
Once in the edit mode pressing the wheel again causes the
editable field to be highlighted. Turning the wheel clockwise
while the editable field is highlighted causes the value to be
increased. Turning the wheel counter-clockwise while the
editable field is highlighted causes the value to be decreased.
The faster the wheel is turned the faster the value is increased
or decreased. Pressing the wheel again cause the new value
to be saved and the keypad/display to leave the edit mode and
return to the navigation mode.
www.DaikinApplied.com

Smoke and Fire Protection

The potential risk of smoke, fire, or fumes entering the unit can result in
serious injury, death, and property damage
Daikin optionally offers factory installed outdoor air, return
air, and exhaust air dampers as well as smoke detectors in
the supply and return air openings, complete with wiring and
control. These components often are used in the building's
smoke, fume, and fire protection systems. However, due to
the wide variation in building design and ambient operating
conditions into which our units are applied, we do not represent
or warrant that our products will be fit and sufficient for smoke,
fume, and fire control purposes. The owner and a fully qualified
building designer are responsible for meeting all local and
NFPA building code requirements with respect to smoke, fume,
and fire control.
Smoke Detectors
Field installed smoke detectors in the return air ductwork or
the supply air ductwork can be coordinated with the unit's
operation through the unit controller's binary input. This input
is wired to TB2 and the supply air smoke detector can be
wired between terminals 103 and 104 and the return air smoke
detector can be wired between terminals 104 and 105. The T2
transformer supplies 24 V (ac) across each of these terminals
and a dry set of contacts can be wired to these terminals
respectively.
Factory installed smoke detectors have similar wiring and the
control sequence is as follows:
When smoke is detected by either sensor, the normally closed
sensor contacts open. This removes power from binary input
on the main control board.
The MicroTech 4 controller responds by shutting down the
unit. The controller is placed in the Alarm Off state and cannot
be restarted until the alarm is manually cleared. Refer to the
operation manual supplied with the unit for information on
clearing alarms.
The smoke detectors must be reset manually once they have
been tripped. Power must be cycled to the smoke detector to
reset.