Daikin Rebel Applied DPSA Installation And Start-Up Manual page 58

Packaged rooftop heating and cooling 30 to 52 tons r-410a refrigerant
Hide thumbs Also See for Rebel Applied DPSA:
Table of Contents

Advertisement

Figure 63: Commission Unit Menu Structure
Commission Unit
Unit Set-Up
Timer Settings
SAF Set-Up
RF/EF Set-Up
Htg/Clg ChgOvr Set-Up
Cooling Set-Up
Econo Set-Up
OA Damper Set-Up
Heating Set-Up
Dehum Set-Up
Humidity Sensor Set-Up
Energy Rec Set-Up
Relief Damper Set-Up
Space Sensor Set-Up
Configurable IO
Alarm/Event Config
IM 1287 • REBEL APPLIED ROOFTOP
Unit Set-Up
SAF Set-Up
Eng Units= English
SAF Ctrl= CAV
UnitName= xxxxxxxx
Speed Control
Loc Space T Cfg= Sen1
Rem SAF Cap= 33%
Emerg Stop= ManClr
DSP Control
SAF DuctPress= X.Xin
SAF DSP Spt= 1.0in
SAF DSP DB= 0.1in
1 Zone VAV Control
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Timer Settings
Occ Htg Spt= 68.0°F
Start Up= 180s
Occ Clg DB= 2.0°F
Recirculate= 180s
Occ Hlg DB= 2.0°F
Clg Stg Time= 5min
CO2 Control
Htg Stg Time= 5min
Min SAF PPM= 800ppm
Zero OA Time= 0m
Max SAF PPM= 1100ppm
Tnt Ovrd Incr= 120min
Min PPM Cap= 50%
Post Heat= 0s
Max PPM Cap= 100%
Low DAT= 6min
Flow Control
Service Time= 0min
OA Flow= XXXXXCFM
OA Flow Spt= 20
OA Flow DB= 3%
SAF Flow= XXXXXCFM
SAF Flow Spt= 2000CFM
SAF Flow DB= 3%
BSP Control
Bldg Press= X.XXin
BldgSP Spt= 0.05in
BSP DB= 0.010in
SAF Setup
Max SAF Hz= 60Hz
Max SAF RPM= 2600RPM
Min Clg Spd= 40%
Max Clg Spd= 100%
Min Htg Spd= 40%
Max Htg Spd= 100%
VAVBox Out=___________
SAF Status=____________
SAF1 Status=___________
SAF2 Status=___________
SAF3 Status=___________
SAF4 Status=___________
58
Unit Operation
RF/EF Set-Up
Htg/Clg ChgOvr Set-Up
RF/EF Ctrl= BSP
Ctrl Temp Src= RAT
Speed Control
RemSptSrc= None
RFEF Cap= 5%
Control Temp= XXX°F
BSP Control
Occ Clg Spt= 72.0°F
Bldg Press= X.XXin
Occ Htg Spt= 68.0°F
BldgSP Spt= 0.05in
Occ Clg DB= 2.0°F
BSP DB= 0.010in
Occ Hlg DB= 2.0°F
Fan Tracking Control
CalRemSpt@10°C=No
CalRemSpt@50°F=No
Sup Fan Max= 100%
CalRemSpt@30°C=No
RFEF @ SF Max= 95%
CalRemSpt@86°F=No
Sup Fan Min= 30%
DemandShed=Enable
RFEF @ SF Min= 25%
RAF DSP Control
RAF DuctPress= X.X
RAF DSP Spt= -1.0 in
RAF DSP DB= 0.10in
Flow Control
RFEF Flow= XXXXXCFM
Cooling Set-Up
RFEF Flow SPT= 2000CFM
Circ1 CmpState=________
RFEF Flow DB= 3%
Circ2 CmpState=________
Flow Diff Control
FCmp1=_______________
SAF Flow= XXXXXCFM
FCmp2=_______________
RFEF Flow= XXXXXCFM
FCmp3=_______________
Min Flow Diff= 0CFM
FCmp4=_______________
Max Flow Diff= 0CFM
FCmp5=_______________
SAF Lo Flow= 150CFM
FCmp6=_______________
SAF Hi Flow= 748CFM
Control Temp= XXX°F
Flow Diff Spt= XXXXCFM
Occ Clg Spt= 72.0°F
Flow Diff DB= 15 CFM
Occ Htg Spt= 68.0°F
OAD Position Control
Disch Air= XXX.X°F
ExhOnOAPos= 40%
DAT Clg Spt= 72.0°F
ExhMxOAPos= 100%
DAT Clg DB= 2.0°F
RFEF Setup
EffSpactT= XXX°F
Max RFEF Hz= 60Hz
Unocc Clg Spt= 85.0°F
Max RFEF RPM= 2600RPM
Unocc Dif f= 3.0°F
Min RFEF Cap= 5%
Clg Stage Time= 5min
Max RFEF Cap= 100%
OA Temp= XXX.X°F
RFEF Status=______________
Clg Lo OAT Lck= 25°F
RFEF1 Status=_____________
OAT Diff= 2°F
RFEF2 Status=_____________
Min Clg Spt= 55.0°F
RFEF3 Status=_____________
Min Clg Spt @= 0
RFEF4 Status=_____________
Clg Reset= None
Max Clg Spt= 65.0°F
Max Clg Spt @= 100
DXBP LCTSpt = 52.0°F
DXBP LCTDB = 2.0°F
DXBPLCTSptReset =None
DXBPMinLCTSpt = 45.0°F
DXBPMinLCTSpt@ = 0
DXBPMaxLCTSpt = 52.0°F
DXBPMaxLCTSpt@ = 100
www.DaikinApplied.com