3.6.3
3.6.4
70
Warning
Leave the water heater electrically isolated until you are ready to commission it.
1. Connect live L
, L
and L
1
2
terminal block as shown in the table (3.8.2 "Preparation").
2. Connect earth ( ) to the earth rail under the live-connections.
Note
For safety reasons the door of the control unit is equipped with a safety switch. When
opening the door the power to the elements is interrupted.
Connecting solar collector sensor
Note
This sensor must be mounted in the solar collector; refer to the solar collector installation
manual.
Connect the sensor (S
) to the water heater as follows:
1
1. Connect the sensor to terminal 5 and 6.
2. Fit the cables in the strain relief.
Important
When the supplied cable is not long enough, the cable can be extended to a maximum
length of a 100 meter. When this length is exceeded data can be lost.
Connecting bottom tank sensor
Connect the sensor (S
) to the water heater as follows:
2
1. Connect the sensor to terminals 7 and 8.
2. Fit the cables in the strain relief.
, of the power cable to terminals L
3
Installation-, user and service manual
, L
and L
of the
1
2
3