Operating Instructions
Proline Promass 83
PROFIBUS DP/PA
Coriolis Mass Flow Measuring System
8
BA063D/06/en/03.05
50100078
Valid as of version
PROFIBUS DP V 3.00.XX (device software)
PROFIBUS PA V 2.03.XX (device software)

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promass 83

  • Page 1 Operating Instructions Proline Promass 83 PROFIBUS DP/PA Coriolis Mass Flow Measuring System BA063D/06/en/03.05 50100078 Valid as of version PROFIBUS DP V 3.00.XX (device software) PROFIBUS PA V 2.03.XX (device software)
  • Page 2 Brief operating instructions Proline Promass 83 PROFIBUS DP/PA Brief operating instructions These brief operating instructions show you how to configure your measuring device quickly and easily: Safety instructions Page 9 ff. ▼ Installation Page 15 ff. ▼ Wiring Page 26 ff.
  • Page 3 Proline Promass 83 PROFIBUS DP/PA Brief operating instructions Data storage Page 115 ff. The configuration of the transmitter can be stored on the integrated T–DAT data storage device. Note! For time-saving commissioning, the settings stored in the T–DAT can be transmitted: ▼...
  • Page 4 Brief operating instructions Proline Promass 83 PROFIBUS DP/PA QUICK SETUP “Commissioning” Note! More detailed information on running Quick Setup menus, especially for devices without a local display, can be found in the “Commissioning” section. see Page 58 1002 XXX.XXX.XX Quick Setup...
  • Page 5 Proline Promass 83 PROFIBUS DP/PA Brief operating instructions Note! • The display returns to the cell SETUP COMMISSIONING (1002) if you press the ESC key combination during parameter interrogation. The stored parameters remain valid. • The “Commissioning” Quick Setup must be carried out before one of the Quick Setups explained below is run.
  • Page 6 Brief operating instructions Proline Promass 83 PROFIBUS DP/PA Endress+Hauser...
  • Page 7: Table Of Contents

    Proline Promass 83 PROFIBUS DP/PA Table of contents Table of contents Safety instructions ....9 Operation ..... . 39 Designated use .
  • Page 8 Proline Promass 83 PROFIBUS DP/PA Table of contents PROFIBUS DP cyclic data exchange ... . 90 Technical data ....147 6.7.1 Block model .
  • Page 9: Safety Instructions

    Strict compliance with the instructions in the Operating Instructions is mandatory. • Endress+Hauser will be happy to assist in clarifying the chemical resistance properties of parts wetted by special fluids, including fluids used for cleaning. However the user is responsible for the choice of fluid wetted materials as regards to their in-process resistance to corrosion.
  • Page 10: Return

    Safety instructions Proline Promass 83 PROFIBUS DP/PA • The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions. Return The following procedures must be carried out before a flowmeter requiring repair or calibration, for example, is returned to Endress+Hauser: •...
  • Page 11: Identification

    Proline Promass 83 PROFIBUS DP/PA Identification Identification Device designation The “Promass 80/83” flow measuring system consists of the following components: • Promass 80 or 83 transmitter • Promass F, Promass M, Promass E, Promass A, Promass H or Promass I sensor Two versions are available: •...
  • Page 12: Nameplate Of The Sensor

    Identification Proline Promass 83 PROFIBUS DP/PA 2.1.2 Nameplate of the sensor ENDRESS+HAUSER PROMASS F XXF25-XXXXXXXXXXXX Order Code: 12345678901 Ser.No.: ABCDEFGHJKLMNPQRST TAG No.: DN25 / 1" 2.5100 / -11 K-factor: Size : DN25 / 1" EN (DIN) PN100 1.4539 / 904L Materials: 200°C / 392°F...
  • Page 13: Nameplate For Connections

    Proline Promass 83 PROFIBUS DP/PA Identification 2.1.3 Nameplate for connections active See operating manual passive Betriebsanleitung beachten normally open contact Observer manuel d'instruction normally closed contact 12345678912 Ser.No.: L1/L+ Supply / Versorgung / N/L- Tension d'alimentation 26 = A (RS485)
  • Page 14: Certificates And Approvals

    Laboratory Procedures” and with the EMC requirements of EN 61326/A1. The measuring system described in these Operating Instructions thus complies with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
  • Page 15: Installation

    Proline Promass 83 PROFIBUS DP/PA Installation Installation Incoming acceptance, transport and storage 3.1.1 Incoming acceptance On receipt of the goods, check the following points: • Check the packaging and the contents for damage. • Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 16: Storage

    Installation Proline Promass 83 PROFIBUS DP/PA 3.1.3 Storage Note the following points: • Pack the measuring device in such a way as to protect it reliably against impact for storage (and transportation). The original packaging provides optimum protection. • The permissible storage temperature is –40...+80 °C (preferably +20 °C).
  • Page 17 Proline Promass 83 PROFIBUS DP/PA Installation The proposed configuration in the following diagram, however, permits installation in a vertical pipeline. Pipe restrictors or the use of an orifice plate with a smaller cross-section than the nominal diameter prevent the sensor from running empty during measurement.
  • Page 18: Orientation

    Installation Proline Promass 83 PROFIBUS DP/PA 3.2.3 Orientation Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of flow (direction in which the fluid flows through the pipe). Orientation Promass A Vertical: Recommended orientation with upward direction of flow.
  • Page 19 Proline Promass 83 PROFIBUS DP/PA Installation Orientation Promass F, M, E, H, I Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of flow (direction in which the fluid flows through the pipe).
  • Page 20: Heating

    ≥ 300 – Relative magnetic permeability µ – Plate thickness d * 0.35 mm • Information on permissible temperature ranges → Page 158 Special heating jackets which can be ordered as accessories from Endress+Hauser are available for the sensors. Endress+Hauser...
  • Page 21: Thermal Insulation

    Proline Promass 83 PROFIBUS DP/PA Installation 3.2.5 Thermal insulation Some fluids require suitable measures to avoid loss of heat at the sensor. A wide range of materials can be used to provide the required thermal insulation. max. 60 max. 60 F06-83FHTxxx-06-00-xx-xx-001 Fig.
  • Page 22: Installation Instructions

    Installation Proline Promass 83 PROFIBUS DP/PA Installation instructions 3.3.1 Turning the transmitter housing Turning the aluminium field housing Warning! The turning mechanism in devices with EEx d/de or FM/CSA Cl. I Div. 1 classification is not the same as that described here. The procedure for turning these housings is described in the Ex-specific documentation.
  • Page 23: Installing The Wall-Mount Transmitter

    Proline Promass 83 PROFIBUS DP/PA Installation 3.3.2 Installing the wall-mount transmitter housing There are various ways of installing the wall-mount transmitter housing: • Mounted directly on the wall • Installation in control panel (separate mounting set, accessories) → Page 24 •...
  • Page 24 Installation Proline Promass 83 PROFIBUS DP/PA Installation in control panel Prepare the opening in the panel as illustrated in the diagram. Slide the housing into the opening in the panel from the front. Screw the fasteners onto the wall-mount housing.
  • Page 25: Turning The Local Display

    Proline Promass 83 PROFIBUS DP/PA Installation 3.3.3 Turning the local display Unscrew cover of the electronics compartment from the transmitter housing. Press the side latches on the display module and remove the module from the electronics compartment cover plate. Rotate the display to the desired position (max. 4 x 45° in both directions), and reset it onto the electronics compartment cover plate.
  • Page 26: Wiring

    Proline Promass 83 PROFIBUS DP/PA Wiring Warning! When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to these Operating Instructions. Please do not hesitate to contact your Endress+Hauser sales office if you have any questions. PROFIBUS cable specifications 4.1.1 PROFIBUS DP cable specifications Two versions of the bus line are specified in IEC61158.
  • Page 27: Profibus Pa Cable Specifications

    Proline Promass 83 PROFIBUS DP/PA Wiring Spurs Note the following points: • Length of spurs < 6.6 m (at max.1.5 MBit/s) • No spurs should be used for transmission rates >1.5 MBit/s. The line between the connector and the bus driver is described as a spur. Experience has shown that you should proceed with caution when configuring spurs.
  • Page 28 Wiring Proline Promass 83 PROFIBUS DP/PA Maximum overall cable length The maximum network expansion depends on the type of protection and the cable specifications. The overall cable length combines the length of the main cable and the length of all spurs (>1 m).
  • Page 29: Shielding And Grounding

    Proline Promass 83 PROFIBUS DP/PA Wiring 4.1.3 Shielding and grounding When planning the shielding and grounding for a fieldbus system, there are three important points to consider: • Electromagnetic compatibility (EMC) • Explosion protection • Safety of the personnel To ensure the optimum electromagnetic compatibility of systems, it is important that the system components and above all the cables, which connect the components, are shielded and that no portion of the system is unshielded.
  • Page 30: Connecting The Remote Version

    Wiring Proline Promass 83 PROFIBUS DP/PA Connecting the remote version 4.2.1 Connecting connecting cable for sensor/transmitter Warning! • Risk of electric shock. Switch off the power supply before opening the device. Do not install or wire the device while it is connected to the power supply.
  • Page 31: Connecting The Measuring Unit

    Proline Promass 83 PROFIBUS DP/PA Wiring Connecting the measuring unit 4.3.1 Terminal assignment Note! The electrical values of the inputs and outputs can be found in the “\Technical data” section. PROFIBUS DP " Caution! Only certain combinations of submodules (see Table) on the I/O board are permissible. The...
  • Page 32: Transmitter Connection

    Wiring Proline Promass 83 PROFIBUS DP/PA 4.3.2 Transmitter connection Warning! • Risk of electric shock. Switch off the power supply before opening the device. Do not install or wire the device while it is connected to the power supply. Failure to comply with this precaution can result in irreparable damage to the electronics.
  • Page 33: Profibus Dp Connection Diagram

    Proline Promass 83 PROFIBUS DP/PA Wiring 4.3.3 PROFIBUS DP connection diagram Permanent assignment I/O board (order version 83***-***********J) (+5 V) N (L–) (DGND) L1 (L+) A (RS485) B (RS485) B (RS485) A (RS485) (DGND) (+5 V) 20 21 22 23...
  • Page 34 Wiring Proline Promass 83 PROFIBUS DP/PA Flexible assignment I/O boards (order version 83***-***********V and 83***-***********P) (L–) A (RS485) (L+) B (RS485) B (RS485) A (RS485) + – + – + – – 20 21 22 23 24 25 26 27 –...
  • Page 35: Profibus Pa Connection Diagram

    Proline Promass 83 PROFIBUS DP/PA Wiring 4.3.4 PROFIBUS PA connection diagram Permanent assignment I/O boards (order version 83***-***********F and 83***-***********H) N (L–) PA (+) L1 (L+) PA (–) PA (–) PA (+) 20 21 22 23 24 25 26 27...
  • Page 36 • Existing cable infrastructures can be used and expanded instantly, e.g. when constructing new star distributors using 4-channel or 8-channel distribution modules. The device can therefore be supplied with the option of a ready-mounted fieldbus connector. Fieldbus connectors for retrofitting can be ordered from Endress+Hauser as a spare part. → Page 117 F06-xxxPBxxx-04-xx-xx-xx-000 Fig.
  • Page 37: Degree Of Protection

    Proline Promass 83 PROFIBUS DP/PA Wiring Technical data (fieldbus connector): Connection cross section 0.75 mm Connector thread PG 13.5 Degree of protection IP 67 in accordance with DIN 40 050 IEC 529 Contact surface CuZnAu Housing material Cu Zn, surface Ni...
  • Page 38: Post-Connection Check

    Wiring Proline Promass 83 PROFIBUS DP/PA Post-connection check Perform the following checks after completing electrical installation of the measuring device: Device condition and specifications Notes Are cables or the device damaged (visual inspection)? Electrical connection Notes Does the supply voltage match the specifications on the nameplate? 85...260...
  • Page 39: Operation

    Proline Promass 83 PROFIBUS DP/PA Operation Operation Quick operation guide The user has a number of options for configuring and commissioning the device: Local display (option) → Page 40 The local display enables you to read all important variables directly at the measuring point, configure device-specific parameters in the field and perform commissioning.
  • Page 40: Local Display

    Operation Proline Promass 83 PROFIBUS DP/PA Local display 5.2.1 Display and operating elements The local display enables you to read all important parameters directly at the measuring point and configure the device using the “Quick Setup” or the function matrix.
  • Page 41: Display (Operating Mode)

    Proline Promass 83 PROFIBUS DP/PA Operation 5.2.2 Display (operating mode) The display area consists of three lines in all; this is where measured values are displayed, and/or status variables (direction of flow, bar graph, etc.). You can change the assignment of display lines to different variables to suit your needs and preferences (→...
  • Page 42: Icons

    Operation Proline Promass 83 PROFIBUS DP/PA 5.2.4 Icons The icons which appear in the field on the left make it easier to read and recognise measured variables, device status, and error messages. Icon Meaning Icon Meaning System error Process error...
  • Page 43 Proline Promass 83 PROFIBUS DP/PA Operation Icon Meaning Icon Meaning Batching quantity upwards Batching quantity downwards a0001201 a0001202 Batch quantity Total batching quantity a0001204 a0001203 Fluid temperature Batch counter (x times) a0001205 a0001207 PROFIBUS communication active Display value e.g. via Fieldcare...
  • Page 44: Controlling The Batching Processes Using The Local Display

    Operation Proline Promass 83 PROFIBUS DP/PA 5.2.5 Controlling the batching processes using the local display Filling processes can be carried out directly by means of the local display with the aid of the optional “(Batching)” software package (F–CHIP, accessories → Page 117). Therefore, the device can be fully deployed in the field as a “batch controller”.
  • Page 45: Brief Operating Instructions To The Function Matrix

    Proline Promass 83 PROFIBUS DP/PA Operation Brief operating instructions to the function matrix Note! • See the general notes → Page 46 • Function descriptions * see the “Description of Device Functions” manual” HOME position → F → Entry into the function matrix Select a block (e.g.
  • Page 46: General Notes

    • If programming is disabled and the P operating elements are pressed in any function, a prompt for the code automatically appears on the display. • If “0” is entered as the customer's code, programming is always enabled! • The Endress+Hauser service organisation can be of assistance if you mislay your personal code. " Caution! Changing certain parameters such as all sensor characteristics, for example, influences numerous functions of the entire measuring system, particularly measuring accuracy.
  • Page 47: Error Messages

    Proline Promass 83 PROFIBUS DP/PA Operation Error messages 5.4.1 Type of error Errors that occur during commissioning or measuring are displayed immediately. If two or more system or process errors occur, the error with the highest priority is the one shown on the display.
  • Page 48: Operating Options

    Proline Promass 83 PROFIBUS DP/PA Operating options 5.5.1 Fieldcare Fieldcare is Endress+Hauser’s FDT-based plant asset management tool and allows the configuration and diagnosis of intelligent field devices. By using status information, you also have a simple but effective tool for monitoring devices. 5.5.2 Operating program “ToF Tool –...
  • Page 49: Operating Program

    The Fieldcheck tester/simulator is used for testing flowmeters in the field. When used in conjunction with the “ToF Tool – Fieldtool Package” software package, test results can be imported into a database, printed and used for official certification. Contact your Endress+Hauser representative for more information.
  • Page 50 The Fieldcheck tester/simulator is used for testing flowmeters in the field. When used in conjunction with the “ToF Tool – Fieldtool Package” software package, test results can be imported into a database, printed and used for official certification. Contact your Endress+Hauser representative for more information.
  • Page 51: Profibus Dp Hardware Settings

    Proline Promass 83 PROFIBUS DP/PA Operation PROFIBUS DP hardware settings 5.6.1 Configuring the write protection A jumper on the I/O board provides the means of switching hardware write protection on or off. When the hardware write protection is switched on, it is not possible to write to the device parameters via PROFIBUS.
  • Page 52: Configuring The Device Address

    Operation Proline Promass 83 PROFIBUS DP/PA 5.6.2 Configuring the device address The address must always be configured for a PROFIBUS DP/PA device. The valid device addresses are in the range from 0…125. In a PROFIBUS DP/PA network, each address can only be assigned once.
  • Page 53: Configuring The Terminating Resistors

    Proline Promass 83 PROFIBUS DP/PA Operation 5.6.3 Configuring the terminating resistors Note! It is important to terminate the RS485 line correctly at the start and end of the bus segment since impedance mismatch results in reflections on the line which can cause faulty communication transmission.
  • Page 54: Current Output Configuration

    Operation Proline Promass 83 PROFIBUS DP/PA 5.6.4 Current output configuration The current output is configured as “active” or “passive” by means of various jumpers on the I/O board or the current submodule. Warning! Risk of electric shock. Exposed components carry dangerous voltages.
  • Page 55: Relay Output Configuration

    Proline Promass 83 PROFIBUS DP/PA Operation 5.6.5 Relay output configuration The relay contact can be configured as normally open (NO or make) or normally closed (NC or break) contacts by means of two jumpers on the I/O board or on the pluggable submodule. This configuration can be called up at any time with the “ACTUAL STATUS RELAY”...
  • Page 56: Profibus Pa Hardware Settings

    Operation Proline Promass 83 PROFIBUS DP/PA PROFIBUS PA hardware settings 5.7.1 Configuring the write protection A jumper on the I/O board provides the means of switching hardware write protection on or off. When the hardware write protection is switched on, it is not possible to write to the device parameters via PROFIBUS.
  • Page 57: Configuring The Device Address

    Proline Promass 83 PROFIBUS DP/PA Operation 5.7.2 Configuring the device address The address must always be configured for a PROFIBUS DP/PA device. The valid device addresses are in the range from 0…125. In a PROFIBUS DP/PA network, each address can only be assigned once.
  • Page 58: Commissioning

    Commissioning Proline Promass 83 PROFIBUS DP/PA Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist for “Post-installation check” → Page 25 • Checklist for “Post-connection check” Note! When using PROFIBUS PA, please note the following: •...
  • Page 59: Quick Setup

    Proline Promass 83 PROFIBUS DP/PA Commissioning Quick Setup In the case of measuring devices without a local display, the individual parameters and functions must be configured via the configuration program, e.g. Fieldcare or ToF Tool - Fieldtool Package. If the measuring device is equipped with a local display, all the important device parameters for standard operation can be configured quickly and easily by means of the “Commissioning”...
  • Page 60 Commissioning Proline Promass 83 PROFIBUS DP/PA 1002 XXX.XXX.XX Quick Setup Commission 2000 Language HOME-POSITION Pre-setting Selection system units Corr. Vol. flow Temperature Mass flow Volume flow Density Quit 0400 0402 0404 0420 0422 Unit Unit Unit Unit Unit Volume flow...
  • Page 61: Quick Setup "Batching

    Note! This function is only available when the additional “batching” software is installed in the measuring device (order option). You can order this software from Endress+Hauser as an accessory at a later date. → Page 117 This Quick Setup menu guides you systematically through the setup procedure for all the device functions that have to be parameterised and configured for batching operation.
  • Page 62 Commissioning Proline Promass 83 PROFIBUS DP/PA XXX.XXX.XX Quick Setup HOME-POSITION 1005 Batching/Dosing 6402 ON-Value Low flow cut off 6603 Flow damping 6404 Pressure shock suppression 7200 Batch Selector 7201 Batch Name 7203 Batch Quantity 7204 Compensation Quantity Select Relay 1...
  • Page 63 Proline Promass 83 PROFIBUS DP/PA Commissioning “Batching” Quick Setup menu HOME position → F → MEASURED VARIABLE (A) MEASURED VARIABLE → O → QUICK SETUP (B) QUICK SETUP → N → QUICK SETUP BATCHING (1005) Setting to be selected ( P ) Function No.
  • Page 64 Commissioning Proline Promass 83 PROFIBUS DP/PA Low flow cutoff / factory settings (v ∼ 0.04 m/s) Nominal diameter [mm] SI units [kg/h] US units [lb/min] 0.08 0.003 0.40 0.015 1.80 0.066 8.00 0.300 26.00 1.000 15 * 72.00 2.600 72.00 2.600...
  • Page 65: Quick Setup "Pulsating Flow

    Proline Promass 83 PROFIBUS DP/PA Commissioning 6.3.3 Quick Setup “Pulsating Flow” Note! The “Pulsating flow” Quick Setup is only available if the device has a current output or a frequency output. Certain types of pump such as reciprocating, peristaltic and cam-type pumps, for example, create a flow characterised by severe periodic fluctuations .
  • Page 66 Commissioning Proline Promass 83 PROFIBUS DP/PA Performing the “Pulsating flow” Quick Setup This Quick Setup menu guides you systematically through the setup procedure for all the device functions that have to be parameterised and configured for measuring pulsating flows. Note that this has no effect on values configured beforehand, such as measuring range, current range or full scale value.
  • Page 67 Proline Promass 83 PROFIBUS DP/PA Commissioning Pulsating Flow” Quick Setup menu” HOME position → F → MEASURED VARIABLE (A) MEASURED VARIABLE → O → QUICK SETUP (B) QUICK SETUP → N → QS PULS. FLOW (1003) Selection with ( P ) Function No.
  • Page 68: Quick Setup "Gas Measurement

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.3.4 Quick Setup “Gas Measurement” The measuring device is not only suitable for measuring liquid flow. Direct mass measurement based on the Coriolis principle is also possible for measuring the flow rate of gases. For this purpose, the relevant device functions can be configured either by means of a configuration program or the local display.
  • Page 69 Proline Promass 83 PROFIBUS DP/PA Commissioning Quick Setup “Gas Measurement” HOME position → F → MEASURED VARIABLE (A) MEASURED VARIABLE → O → QUICK SETUP (B) QUICK SETUP → N → QS GAS MEASUREMENT (1004) Setting to be selected ( P ) Function No.
  • Page 70: Quick Setup "Communication

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.3.5 Quick Setup “Communication” To establish cyclic data transfer, various arrangements between the PROFIBUS master and slave are required which have to be taken into consideration when configuring various functions. These functions can be configured quickly and easily by means of the “Communication” Quick Setup. The table explains the parameter configuration options in more detail.
  • Page 71 Proline Promass 83 PROFIBUS DP/PA Commissioning Communication” Quick Setup. 6141 SET UNIT TO BUS In this function, the transmission of the configured system units to the automation system can be enabled. By pressing the F key, the measured values and the set system units are transmitted to the automation system.
  • Page 72: Data Back-Up With "T-Dat Save/Load

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.3.6 Data back-up with “T-DAT SAVE/LOAD” The “T-DAT SAVE/LOAD” function can be used to store all the settings and parameters of the device to the T-DAT data storage device. XXX.XXX.XX QUICK SETUP HOME-POSITION 1009...
  • Page 73: Device Configuration

    Proline Promass 83 PROFIBUS DP/PA Commissioning Device configuration 6.4.1 Concentration measurement The measuring device determines three primary variables simultaneously: • Mass flow • Fluid density • Fluid temperature As standard, these measured variables allow other process variables to be calculated, such as volume flow, reference density (density at reference temperature) and corrected volume flow.
  • Page 74 Commissioning Proline Promass 83 PROFIBUS DP/PA ENDRESS+HAUSER HOME POSITION Special Density function functions Configuration 7000 Density function Selection ° API % MASS ° BAUME ° BRIX FLEXIBLE % VOLUME ° PLATO ° BALLING 7001 7007 7007 see separate Expansion Expansion...
  • Page 75 Proline Promass 83 PROFIBUS DP/PA Commissioning Brixgrade (density of hydrous saccharose solution in kg/m °Brix 10°C 20°C 30°C 40°C 50°C 60°C 70°C 80°C 1321.46 1316.56 1311.38 1305.93 1300.21 1294.21 1287.96 1281.52 1352.55 1347.49 1342.18 1336.63 1330.84 1324.80 1318.55 1312.13 1384.58 1379.38...
  • Page 76 Commissioning Proline Promass 83 PROFIBUS DP/PA Example: The following is a concentration table from a reference source. Temperature 10°C 15°C 20°C 25°C 30°C Density 825 kg/m 93.6% 92.5% 91.2% 90.0% 88.7% 840 kg/m 89.3% 88.0% 86.6% 85.2% 83.8% 855 kg/m 84.4%...
  • Page 77 Proline Promass 83 PROFIBUS DP/PA Commissioning Calculation type “% MASS 2D” or “% VOLUME 2D” For this type of calculation, the relationship between the two variables concentration and reference density must be known (2-dimensional), e.g. by a table. In this way, the concentration can be calculated from the measured density and temperature values by means of the following formula (the coefficients A0, A1, etc.
  • Page 78: Advanced Diagnostic Functions

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.4.2 Advanced diagnostic functions Changes to the measuring system, e.g. coating build-up or corrosion and abrasion on the measuring tubes can be detected at an early stage by means of the optional software package “Advanced Diagnostics”...
  • Page 79 Proline Promass 83 PROFIBUS DP/PA Commissioning Triggering warning messages If required, a limit value can be assigned to all the process/device parameters relevant to the diagnostic functions. A warning message is triggered if this limit value is exceeded → function WARNING MODE (7403).
  • Page 80: Commissioning The Profibus Interface

    Commissioning Proline Promass 83 PROFIBUS DP/PA Commissioning the PROFIBUS interface Note! • All functions required for commissioning are described in detail in the “Description of Device Functions” manual which is a separate part of these Operating Instructions. • A code (factory setting: 83) must be entered to change device functions, numerical values or factory settings.
  • Page 81 Proline Promass 83 PROFIBUS DP/PA Commissioning Configuration of the Analog Input function blocks 1…6: Promass 83 has six Analog Input function blocks. The following example describes the configuration of Analog Input function block 1. • In the “CHANNEL” parameter, select the measured variable (e.g. mass flow) to be transmitted cyclically to the PROFIBUS master by means of Analog Input function block 1: BASIC FUNCTION (G) →...
  • Page 82 Commissioning Proline Promass 83 PROFIBUS DP/PA Measured variable ID for “CHANNEL” parameter Batch counter 1348 Total batching quantity 1349 Batching time 1354 The following measured variables are available when the additional “advanced diagnostics” software is installed (order option) Mass flow deviation...
  • Page 83 Proline Promass 83 PROFIBUS DP/PA Commissioning Select the operating mode (GSD file) which should be used for cyclic communication with the PROFIBUS master. BASIC FUNCTION (G) → PROFIBUS DP (GBA) → OPERATION (614) → SELECTION GSD (6140) → Select: – MANUFACT. SPEC. (factory setting): Promass 83 measuring device is operated in the manufacturer-specific mode.
  • Page 84: Profibus Pa Commissioning

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.5.2 PROFIBUS PA commissioning The following steps must be carried out in the sequence specified: Check the hardware write protection: Note! – The ”WRITE PROTECTION” parameter indicates whether write access to the device is possible via PROFIBUS.
  • Page 85 Proline Promass 83 PROFIBUS DP/PA Commissioning Configuration of totalizers 1-3: Promass 83 has 3 totalizers. The following example applies to totalizer 1. • In the “CHANNEL” parameter, select the measured variable (e.g. mass flow) to be transmitted to the PROFIBUS master as the totalizer value 1: BASIC FUNCTION (G) →...
  • Page 86: Profibus System Integration

    Commissioning Proline Promass 83 PROFIBUS DP/PA PROFIBUS system integration 6.6.1 Device master file (GSD file) For PROFIBUS network configuration, the device master file (GSD file) is needed for every bus user (PROFIBUS slave). The GSD file contains a description of the properties of a PROFIBUS device, such as supported data transmission rate and number of input and output data.
  • Page 87 Each device receives an ID number from the Profibus User Organisation (PNO). The name of the Device Master File (GSD file) and the associated files is derived from this. For Endress+Hauser, this ID No. starts with the manufacturer ID 15xx, followed by corresponding device ID.
  • Page 88 Commissioning Proline Promass 83 PROFIBUS DP/PA Contents of the download file from the Internet and the CD-ROM: • All Endress+Hauser GSD files (standard and extended format) • Endress+Hauser type files • Endress+Hauser bitmap files • Useful information relating to the devices...
  • Page 89: Promass 63 With Profile Version 2.0

    Promass 83 can be used as a replacement device without having to reconfigure the PROFIBUS DP network. In the event of a device being replaced, Proline Promass 83 supports the compatibility of the cyclic data with the previous Promass 63 model with Profile Versions 2.0 as follows: •...
  • Page 90: Profibus Dp Cyclic Data Exchange

    Commissioning Proline Promass 83 PROFIBUS DP/PA PROFIBUS DP cyclic data exchange 6.7.1 Block model The block model illustrated shows which input and output data Promass 83 provides for cyclic data exchange via PROFIBUS DP. Measured variable 1 Physical XXX.XXX.XX Local...
  • Page 91 Proline Promass 83 PROFIBUS DP/PA Commissioning Assignment of the measured variables to the AI module The AI module can transmit different measured variables to the PROFIBUS master system. The measured variables are assigned to the Analog Input function blocks 1…6 by means of the local display or with the aid of a class 2 master (operating program) in the “CHANNEL”...
  • Page 92 Commissioning Proline Promass 83 PROFIBUS DP/PA Measured variable ID for “CHANNEL” parameter °Baume °API °Plato 1175 °Balling °Brix The following measured variables are available when the additional “viscosity” software is installed (order option) Dyn. viscosity 1177 Kin. viscosity 1178 T. comp. dyn. viscosity 1179 T.
  • Page 93 Proline Promass 83 PROFIBUS DP/PA Commissioning TOTAL module - cyclic transmission of totalizer values The measuring device has three totalizer function blocks. The totalizer values can be read out cyclically by the automation system by means of the TOTAL module. Here, the cyclic transmission of totalizer values to the automation system is effected in data blocks of 5 bytes.
  • Page 94 Commissioning Proline Promass 83 PROFIBUS DP/PA Note! The measured variables for the software option “concentration measurement” are only available if the appropriate additional software is installed in the device. If the measured variable is selected even if the additional software is not installed, the value “0” is transmitted to the automation device (PROFIBUS master) for the measured variable.
  • Page 95 Proline Promass 83 PROFIBUS DP/PA Commissioning Data structure of the module combinations supported The modules shown in the table can be integrated in the automation system in conjunction with the TOTAL module (totalizer value) by means of the following module combinations:...
  • Page 96 Commissioning Proline Promass 83 PROFIBUS DP/PA CONTROL_BLOCK module - cyclic control of device functions By means of the CONTROL_BLOCK module, the measuring device is able to process device-specific control variables in cyclic data exchange (e.g. switching on positive zero return).
  • Page 97 Proline Promass 83 PROFIBUS DP/PA Commissioning Note! The control (e.g. switching on positive zero return) is executed by cyclic data exchange if the output byte switches from “0” to the bit pattern in question. The output byte must always switch from “0”.
  • Page 98 Commissioning Proline Promass 83 PROFIBUS DP/PA BATCHING_FIX_COMP_QUANTITY module - cyclic transmission of the fixed compensation quantity (tail quantity) A positive or negative compensation quantity (32-bit floating-point number) incl. status can be cyclically transmitted from the automation system to the measuring device by means of the BATCHING_FIX_COMP__QUANTITY module.
  • Page 99: Configuration Information For Integrating Modules

    Proline Promass 83 PROFIBUS DP/PA Commissioning 6.7.3 Configuration information for integrating modules Promass 83 is a modular PROFIBUS slave. In contrast to a compact slave, the structure of a modular slave is variable - it consists of several individual modules. In the GSD file, the individual modules are described with their individual properties.
  • Page 100: Configuration Examples With

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.7.4 Configuration examples with Simatic S7 HW-Konfig Example 1: a0002662 Fig. 45: Complete configuration using the Promass 83 GSD file (manufacturer-specific GSD file) It is essential to adhere to the following sequence when configuring the modules into the...
  • Page 101 Proline Promass 83 PROFIBUS DP/PA Commissioning Slot Byte length Byte length Module Description sequence input data output data Totalizer function block 1 (slot 7) Totalizer function block 2 (slot 8) SETTOT_MODETOT_TOTAL Totalizer function block 3 (slot 9) Totalizer configuration: SETTOT → totalizer control MODETOT →...
  • Page 102 Commissioning Proline Promass 83 PROFIBUS DP/PA Example 2: a0002664 Fig. 46: In this configuration example, modules that are not needed are replaced by the EMPTY_MODULE. The Promass 83 GSD file is used. With this configuration, the Analog Input function block 1(slot 1), the totalizer value TOTAL (slot 7) and the cyclic control of device functions CONTROL_BLOCK (slot 11) are activated.
  • Page 103: Profibus Pa Cyclic Data Exchange

    Proline Promass 83 PROFIBUS DP/PA Commissioning PROFIBUS PA cyclic data exchange 6.8.1 Block model The block model illustrated shows which input and output data Promass 83 provides for cyclic data exchange via PROFIBUS PA. Physical XXX.XXX.XX Local Block Display Analog Input 1...
  • Page 104 Commissioning Proline Promass 83 PROFIBUS DP/PA Assignment of the measured variables to the AI module The measured variables are permanently assigned to the six Analog Input function blocks (AI) and cannot be changed. Module Analog Input Measured variable “CHANNEL” Unit factory...
  • Page 105 Proline Promass 83 PROFIBUS DP/PA Commissioning The following settings are possible: Measured variable ID for “CHANNEL” parameter Mass flow 277 (factory setting TOTAL 1...3) Volume flow Corrected volume flow Note! In the case of customised settings, the units can deviate from the factory setting.
  • Page 106 Commissioning Proline Promass 83 PROFIBUS DP/PA Data structure of the module combinations supported The modules shown in the table can be integrated in the automation system in conjunction with the TOTAL module (totalizer value) by means of the following module combinations:...
  • Page 107 Proline Promass 83 PROFIBUS DP/PA Commissioning CONTROL_BLOCK module - cyclic control of device functions By means of the CONTROL_BLOCK module, the measuring device is able to process device-specific control variables in cyclic data exchange (e.g. switching on positive zero return).
  • Page 108: Configuration Information For Integrating Modules

    Commissioning Proline Promass 83 PROFIBUS DP/PA 6.8.3 Configuration information for integrating modules Promass 83 is a modular PROFIBUS slave. In contrast to a compact slave, the structure of a modular slave is variable - it consists of several individual modules. In the GSD file, the individual modules are described with their individual properties.
  • Page 109: Configuration Examples With

    Proline Promass 83 PROFIBUS DP/PA Commissioning 6.8.4 Configuration examples with Simatic S7 HW-Konfig Example 1: a0002665 Fig. 48: Complete configuration using the Promass 83 GSD file (manufacturer-specific GSD file) It is essential to adhere to the following sequence when configuring the modules into the...
  • Page 110 Commissioning Proline Promass 83 PROFIBUS DP/PA Slot Byte length Byte length Module Description sequence input data output data Totalizer function block 1 (slot 7) SETTOT_MODETOT_TOTAL Totalizer function block 2 (slot 8) Totalizer function block 3 (slot 9) Totalizer configuration: SETTOT → totalizer control MODETOT →...
  • Page 111 Proline Promass 83 PROFIBUS DP/PA Commissioning Example 2: a0002682 Fig. 49: In this configuration example, modules that are not needed are replaced by the EMPTY_MODULE. The Promass 83 GSD file is used. With this configuration, the Analog Input function block 1(slot 1), the totalizer value TOTAL (slot 7) and the cyclic control of device functions CONTROL_BLOCK (slot 11) are activated.
  • Page 112: Adjust

    Commissioning Proline Promass 83 PROFIBUS DP/PA Adjust 6.9.1 Zero point adjustment All Promass measuring devices are calibrated with state-of-the-art technology. The zero point obtained in this way is printed on the nameplate. Calibration takes place under reference operating conditions. → Page 151 ff.
  • Page 113: Density Adjustment

    Proline Promass 83 PROFIBUS DP/PA Commissioning Performing a zero point adjustment Operate the system until operating conditions have settled. Stop the flow (v = 0 m/s). Check the shut-off valves for leaks. Check that operating pressure is correct. Using the local display, select the ZEROPOINT ADJUSTMENT function in the function matrix: BASIC FUNCTION →...
  • Page 114 Commissioning Proline Promass 83 PROFIBUS DP/PA • Density adjustment changes the factory density calibration values or the calibration values set by the service technician. • The functions outlined in the following instructions are described in detail in the “Description of Device Functions”...
  • Page 115: Purge And Pressure Monitoring Connections

    6.11 Data storage device (HistoROM), F–CHIP At Endress+Hauser, the term HistoROM refers to various types of data storage modules on which process and measuring device data are stored. By plugging and unplugging such modules, device configurations can be duplicated onto other measuring devices to cite just one example.
  • Page 116: Maintenance

    Maintenance Proline Promass 83 PROFIBUS DP/PA Maintenance No special maintenance work is required. Exterior cleaning When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the surface of the housing and the seals. Cleaning with pigs (Promass H, I) If pigs are used for cleaning, it is essential to take the inside diameters of measuring tube and process connection into account.
  • Page 117: Accessories

    Proline Promass 83 PROFIBUS DP/PA Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. The Endress+Hauser service organisation can provide detailed information on the order code of your choice. Device-specific accessories:...
  • Page 118: Service-Specific Accessories

    Accessories Proline Promass 83 PROFIBUS DP/PA Service-specific accessories: Accessory Description Order code Applicator Software for selecting and configuring flowmeters. DKA80 – * Applicator can be downloaded from the Internet or ordered on CD-ROM for installation on a local PC. Contact your Endress+Hauser representative for more information.
  • Page 119: Trouble-Shooting

    Proline Promass 83 PROFIBUS DP/PA Trouble-shooting Trouble-shooting Trouble-shooting instructions Always start trouble-shooting with the following checklist if faults occur after commissioning or during operation. The routine takes you directly to the cause of the problem and the appropriate remedial measures.
  • Page 120 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA Fieldbus voltage Check that a min. bus voltage of 9 V DC is present at terminals 26/27. Permissible range: (only for PROFIBUS PA) 9 ... 32 V DC Check permissible fieldbus length and number of spurs. → Page 26...
  • Page 121: System Error Messages

    Caution! In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair. Important procedures must be carried out before you return a flowmeter to Endress+Hauser. → Page 10 Always enclose a duly completed “Declaration of contamination” form. You will find a preprinted blank of this form at the back of this manual.
  • Page 122: Profibus

    Trouble-shooting Proline Promass 83 PROFIBUS DP/PA • For FAILSAFE_TYPE → LAST GOOD VALUE (factory setting): The following status information is transmitted if a valid output value was available before the failure: Quality code (HEX) Quality status Quality substatus Limits Measured value status 0x44 O.K.
  • Page 123 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S AMP SW EEPROM 0x0F Device Failure Constant Amplifier Cause: $ # 012 EEPROM data System error. Error when accessing data of the...
  • Page 124 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S TRANSM. SW DAT 0x0F Device Failure Constant T-DAT data Cause: $ # 042 inconsistent System error. Error accessing the calibration values stored in the T-DAT.
  • Page 125 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S SAVE T-DAT 0x0F Device Failure Constant Restore from T- Cause: ! # 206 DAT failed System error. Data backup to T-DAT failed, or error when accessing the calibration values stored in the T-DAT.
  • Page 126 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S: STACK PULSE OUT n 0x0F Device Failure Constant Temp. Buf. not Cause: !: # 347...350 cleared The temporarily buffered flow portions (measuring mode for pulsating flow) could not be cleared or output within 60 seconds.
  • Page 127 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S: PULSE RANGE 0x54 UNCERTAIN Engineering O.K. Flow is Out of Cause: !: # 359...362 0x55 Unit Range Range Pulse output: Pulse output frequency is out of range.
  • Page 128 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S FLUIDTEMP.MAX. 0x10 Sensor Failure O.K. Fluid Cause: $ # 382 0x11 Temperature The temperature sensor on the measuring tube is...
  • Page 129 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S OUTL.SENS.DEF. 0x10 Sensor Failure O.K. Outlet Sensor Cause: $ # 386 0x11 Defect One of the measuring tube exciter coils (inlet or...
  • Page 130 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master P TUBE NOT OSC 0X10 Sensor Failure O.K. No oscillation Cause: $ # 587 0x11 possible Extreme process conditions exist. The measuring...
  • Page 131 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting PROFIBUS measured value status Adv. diagnosis Device status message message in Cause/remedy (local display) PROFIBUS master S SIM. FAILSAFE 0x48 UNCERTAIN Substitute set O.K. Simulation Cause ! # 691 0x49 (Substitute set failsafe active...
  • Page 132: Process Error Messages

    Trouble-shooting Proline Promass 83 PROFIBUS DP/PA Process error messages Process errors can be defined as either “Fault” or “Notice” messages and can thereby be weighted differently. This is specified via the function matrix (→ “Description of Device Functions” manual). Note! •...
  • Page 133 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting Device status message PROFIBUS measured value status Adv. diagnosis Cause/remedy (local display) message in PROFIBUS master P: >< BATCH 0x00 Non Specific O.K. Batch Quantity Cause: QUANTITY 0x01 (uncertain EPD calibration not possible as the fluid conductivity is...
  • Page 134 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA Device status message PROFIBUS measured value status Adv. diagnosis Cause/remedy (local display) message in PROFIBUS master P EMPTY PIPE 0x53 UNCERTAIN Sensor Constant Empty pipe Cause: ! # 700 conversion detected The process fluid density is outside the upper or lower not accurate limit values set for empty pipe detection.
  • Page 135: Process Errors Without Messages

    • Nameplate specifications: order code and serial number → Page 11 Return devices to E+H You can return a measuring device to Endress+Hauser for repair or calibration. Always enclose the duly completed “Declaration of contamination” form with the flowmeter. You will find a preprinted blank of this form at the back of this manual.
  • Page 136: Response Of Outputs To Errors

    Trouble-shooting Proline Promass 83 PROFIBUS DP/PA Response of outputs to errors Note! The failsafe mode of totalizers, current, pulse and frequency outputs can be customised by means of various functions in the function matrix. You will find detailed information on these procedures in the “Description of Device Functions”...
  • Page 137: Spare Parts

    Proline Promass 83 PROFIBUS DP/PA Trouble-shooting Spare parts The previous sections contain a detailed trouble-shooting guide. → Page 119 ff. The measuring device, moreover, provides additional support in the form of continuous self- diagnosis and error messages. Fault rectification can entail replacing defective components with tested spare parts. The illustration below shows the available scope of spare parts.
  • Page 138: Profibus Pa

    Trouble-shooting Proline Promass 83 PROFIBUS DP/PA 9.6.2 PROFIBUS PA a0002855 Fig. 53: Spare parts for transmitter Promass 83 PROFIBUS PA (field and wall-mount housings) Power unit board (85...260 V AC, 20...55 V AC, 16...62 V DC) Amplifier board I/O board (COM module), flexible...
  • Page 139: Removing And Installing Printed Circuit

    Proline Promass 83 PROFIBUS DP/PA Trouble-shooting 9.6.3 Removing and installing printed circuit boards Field housing Warning! • Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment.
  • Page 140 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA T / O T / O F06-83xxxxxx-03-06-06-xx-001 Fig. 54: Field housing: removing and installing printed circuit boards Local display Latch Ribbon cable (display module) Screws of electronics compartment cover Aperture for installing/removing boards Power unit board...
  • Page 141 Proline Promass 83 PROFIBUS DP/PA Trouble-shooting Wall-mount housing Warning! • Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. • Risk of damaging electronic components (ESD protection). Static electricity can damage electronic components or impair their operability.
  • Page 142 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA T / O T / O F06-x3MBxxxx-03-03-06-xx-000 Fig. 55: Wall-mount housing: removing and installing printed circuit boards Housing cover Electronics module Ribbon cable (display module) Screws of electronics compartment cover Aperture for installing/removing boards...
  • Page 143: Replacing The Device Fuse

    Proline Promass 83 PROFIBUS DP/PA Trouble-shooting 9.6.4 Replacing the device fuse Warning! Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power supply is switched off before you remove the cover of the electronics compartment. The main fuse is on the power unit board.
  • Page 144: Return

    Endress+Hauser: • Always enclose a duly completed “Declaration of contamination” form. Only then can Endress+Hauser transport, examine and repair a returned device. • Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/155/EEC.
  • Page 145: Software History

    Proline Promass 83 PROFIBUS DP/PA Trouble-shooting Software history Date Software version Changes to software Operating Instructions 02.2005 PROFIBUS DP New PROFIBUS DP I/O Module is launched: 50100077/03.05 3.00.XX – Support of additionale output signals (current, frequency etc.) Software expansion: – Advanced diagnosis –...
  • Page 146 Trouble-shooting Proline Promass 83 PROFIBUS DP/PA Date Software version Changes to software Operating Instructions 03.2002 Communication module: Software expansion: 50100077/04.02 2.00.01 – New error messages: 061, 121, 501 – Extension of control systems in cyclic data exchange Control variables (measuring mode): –...
  • Page 147: Technical Data

    Proline Promass 83 PROFIBUS DP/PA Technical data Technical data 10.1 Technical data at a glance 10.1.1 Applications The measuring device described in these Operating Instructions is to be used only for measuring the mass flow rate of liquids and gases. At the same time, the system also measures fluid density and fluid temperature.
  • Page 148 Technical data Proline Promass 83 PROFIBUS DP/PA Measuring ranges for liquids (Promass H, I): Range for full scale values (liquids) g ...g min(F) max(F) 0...2000 kg/h 0...6500 kg/h 15 * 0...18000 kg/h 0...18000 kg/h 25 * 0...45000 kg/h 0...45000 kg/h 40 * 0...70000 kg/h...
  • Page 149: Profibus Dp Output

    Proline Promass 83 PROFIBUS DP/PA Technical data Recommended full scale values See → Page 159 ff. (“Limiting flow”) Operable flow range Greater than 1000 : 1. Flows above the preset full scale value do not overload the amplifier, i.e. totalizer values are registered correctly.
  • Page 150: Power Supply

    Technical data Proline Promass 83 PROFIBUS DP/PA Relay output De-energised by fault or power supply failure PROFIBUS DP/PA Status and error messages according to profibus Profile Version 3.0. Load See “Output signal” Relay output: Normally closed (NC or break) or normally open (NO or make) contacts available (default: relay 1 = NO, relay 2 = NC), max.
  • Page 151: Performance Characteristics

    Proline Promass 83 PROFIBUS DP/PA Technical data 10.1.6 Performance characteristics Reference operating Error limits following ISO/DIS 11631: conditions • 20...30 °C; 2...4 bar • Calibration systems as per national norms • Zero point calibrated under operating conditions • Field density calibrated (or special density calibration) Maximum measured error The following values refer to the pulse/frequency output.
  • Page 152 Technical data Proline Promass 83 PROFIBUS DP/PA Volume flow (liquid) Promass F: ±0.15% ± [(zero point stability / measured value) x 100]% o.r. Promass M, A: ±0.25% ± [(zero point stability / measured value) x 100]% o.r. Promass E: ±0.45% ± [(zero point stability / measured value) x 100]% o.r.
  • Page 153 Proline Promass 83 PROFIBUS DP/PA Technical data Zero point stability (Promass H, I): Maximum full scale Zero point stability value Promass H Promass I in [kg/h] or [l/h] in [kg/h] or [l/h] in [kg/h] or [l/h] 2000 0.20 0.20 6500 0.65...
  • Page 154 Technical data Proline Promass 83 PROFIBUS DP/PA Density (liquid) After field density calibration or under reference conditions: Promass F: ±0.0005 g/cc Promass M, E, A, H: ±0.0010 g/cc Promass I: ±0.0020 g/cc Special density calibration (optional), not for high-temperature version (calibration range = 0.8...1.8 g/cc, 5...80 °C):...
  • Page 155 Proline Promass 83 PROFIBUS DP/PA Technical data Repeatability Mass flow (liquid): Promass F, M, A, H, I: ±0.05% ± [1/2 x (zero point stability / measured value) x 100]% o.r. Promass E: ±0.15% ± [1/2 x (zero point stability / measured value) x 100]% o.r.
  • Page 156 Technical data Proline Promass 83 PROFIBUS DP/PA Density measurement (liquid) Promass F: ±0.00025 g/cc (1 g/cc = 1 kg/l) Promass M, H, E, A: ±0.0005 g/cc Promass I: ±0.001 g/cc Temperature measurement ±0.25 °C ±0.0025 x T (T = fluid temperature in °C)
  • Page 157: Operating Conditions: Installation

    Proline Promass 83 PROFIBUS DP/PA Technical data Promass H, I: Promass H Promass I [% o.r./bar] [% o.r./bar] -0.017 0.006 -0.021 0.004 15 * 0.006 -0.013 0.006 25 * No influence -0.018 No influence 40 * 0.006 -0.020 0.006 * DN 15, 25, 40 “FB” = Full bore versions of Promass I o.r.
  • Page 158: Operating Conditions: Process

    Technical data Proline Promass 83 PROFIBUS DP/PA 10.1.9 Operating conditions: Process Medium temperature range Sensor: Promass F, A, H: –50...+200 °C Promass F (high-temperature version): –50...+350 °C Promass M, I: –50...+150 °C Promass E: –40...+125 °C Seals: Promass F, E, H, I:...
  • Page 159 Proline Promass 83 PROFIBUS DP/PA Technical data Promass H: DN 8...15: 25 bar or 375 psi; DN 25...50: 16 bar or 250 psi Promass I: 40 bar or 600 psi See “Measuring range” section. → Page 147 ff. Limiting flow Select nominal diameter by optimising between required flow range and permissible pressure loss.
  • Page 160 Technical data Proline Promass 83 PROFIBUS DP/PA Pressure loss coefficient for Promass F d[m] 5.35 ⋅ 10 5.70 ⋅ 10 9.60 ⋅10 1.90 ⋅ 10 –3 8.30 ⋅ 10 5.80 ⋅ 10 1.90 ⋅ 10 10.60 ⋅ 10 –3 12.00 ⋅ 10 1.90 ⋅...
  • Page 161 Proline Promass 83 PROFIBUS DP/PA Technical data Pressure loss coefficient for Promass M d[m] 5.53 ⋅ 10 5.2 ⋅ 10 8.6 ⋅10 1.7 ⋅ 10 –3 8.55 ⋅ 10 5.3 ⋅ 10 1.7 ⋅ 10 9.7 ⋅ 10 –3 11.38 ⋅ 10 1.7 ⋅...
  • Page 162 Technical data Proline Promass 83 PROFIBUS DP/PA Pressure loss coefficient for Promass E d[m] 5.35 ⋅ 10 5.70 ⋅ 10 7.91 ⋅10 2.10 ⋅ 10 –3 8.30 ⋅ 10 7.62 ⋅ 10 1.73 ⋅ 10 2.13 ⋅ 10 –3 12.00 ⋅ 10 1.89 ⋅...
  • Page 163 Proline Promass 83 PROFIBUS DP/PA Technical data Pressure loss coefficient for Promass A d[m] 1.1 ⋅ 10 1.2 ⋅ 10 1.3 ⋅10 –3 1.8 ⋅ 10 1.6 ⋅ 10 2.4 ⋅ 10 –3 3.5 ⋅ 10 9.4 ⋅ 10 2.3 ⋅ 10 –3...
  • Page 164 Technical data Proline Promass 83 PROFIBUS DP/PA Pressure loss coefficient for Promass H d[m] 8.51 ⋅ 10 8.04 ⋅ 10 3.28 ⋅10 1.15 ⋅ 10 –3 12.00 ⋅ 10 1.81 ⋅ 10 9.99 ⋅ 10 1.87 ⋅ 10 –3 17.60 ⋅ 10 3.67 ⋅...
  • Page 165 Proline Promass 83 PROFIBUS DP/PA Technical data Pressure loss coefficient for Promass I d[m] 8.55 ⋅ 10 8.1 ⋅ 10 3.9 ⋅10 129.95 ⋅ 10 –3 11.38 ⋅ 10 2.3 ⋅ 10 1.3 ⋅ 10 23.33 ⋅ 10 –3 17.07 ⋅ 10 4.1 ⋅...
  • Page 166: 10.1.10 Mechanical Construction

    Technical data Proline Promass 83 PROFIBUS DP/PA 10.1.10 Mechanical construction Design / dimensions Dimensions and the fitting lengths of the transmitter and sensor are given in the Technical Information. → Page 171 Weight • Compact version: see table below • Remote version –...
  • Page 167 Proline Promass 83 PROFIBUS DP/PA Technical data Material Transmitter housing: • Compact housing: stainless steel 1.4301/304 • Compact housing: powder coated die-cast aluminium • Wall-mount housing: powder coated die-cast aluminium • Remote field housing: powder-coated die-cast aluminium Sensor housing / containment:...
  • Page 168 Technical data Proline Promass 83 PROFIBUS DP/PA Promass M: • Flanges EN 1092-1 (DIN 2501) / ANSI B16.5 / JIS B2238 * stainless steel 1.4404/316L, titanium grade 2 • Flange DIN 11864-2 Form A (flat flange) * stainless steel 1.4404/316L •...
  • Page 169: 10.1.11 Human Interface

    Proline Promass 83 PROFIBUS DP/PA Technical data Promass M: • DN 8...50: titanium grade • DN 80: titanium grade 2 Promass M (high pressure version): • Titanium grade 9 Promass E: • Stainless steel 1.4539/904L Promass A: • Stainless steel 1.4539/904L, Alloy C-22 2.4602/N 06022 Promass H: •...
  • Page 170: 10.1.12 Certificates And Approvals

    CE mark The measuring system is in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Ex approval Information about currently available Ex versions (ATEX, FM, CSA) can be supplied by your E+H Sales Centre on request.
  • Page 171: 10.1.13 Ordering Information

    10.1.14 Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the transmitter and the sensor. → Page 117 The Endress+Hauser service organisation can provide detailed information on the order codes of your choice.
  • Page 172: Index

    Proline Promass 83 PROFIBUS DP/PA Index Index PROFIBUS DP....... 52 PROFIBUS PA .
  • Page 173 Proline Promass 83 PROFIBUS DP/PA Index PROFIBUS PA ......107 MODETOT Icons......... 42 PROFIBUS DP .
  • Page 174 Proline Promass 83 PROFIBUS DP/PA Index Bus structure ....... . 26 Secondary containment Cable specifications .
  • Page 175 Proline Promass 83 PROFIBUS DP/PA Index Write protection PROFIBUS DP ....... 51 PROFIBUS PA .
  • Page 176 Proline Promass 83 PROFIBUS DP/PA Index Endress+Hauser...
  • Page 177 Declaration of Contamination Erklärung zur Kontamination Because of legal regulations and for the safety of our employees and operating equipment, we need the "declaration of contamination", with your signature, before your order can be handled. Please make absolutely sure to include it with the shipping documents, or - even better - attach it to the outside of the packaging.
  • Page 178 www.endress.com/worldwide BA063D/06/en/03.05 50100078 FM+SGML6.0 ProMoDo...