Endress+Hauser Proline Promass 84 Safety Instructions
Endress+Hauser Proline Promass 84 Safety Instructions

Endress+Hauser Proline Promass 84 Safety Instructions

Hart, profibus dp/pa, foundation fieldbus, modbus rs485
Hide thumbs Also See for Proline Promass 84:

Advertisement

Quick Links

Safety Instructions
HART, PROFIBUS DP/PA, FOUNDATION Fieldbus, MODBUS RS485
NEPSI Zone 1, Zone 21
Ex documentation
This document is an integral part of the following Operating Instructions:
• BA059D, Proline Promass 83 HART
• BA063D, Proline Promass 83 PROFIBBUS DP/PA
• BA065D, Proline Promass 83 FOUNDATION Fieldbus
• BA107D, Proline Promass 83 Modbus RS485
Contents
General warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Special conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
COC certificates of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nameplates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Temperature table compact version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Temperature table remote version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas and dust explosion protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Design of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cable entries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connection of remote version connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Terminal assignment and connection data, power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
(intrinsically safe circuits) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
(energy limited circuits/Ex nL/non incendive field wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
(non-intrinsically safe circuits) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Service adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Device fuse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
XA122D/06/en/03.10
71111298
• BA109D, Proline Promass 84 HART
• BA129D, Proline Promass 84 MODBUS RS485

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promass 84

  • Page 1: Table Of Contents

    • BA059D, Proline Promass 83 HART • BA109D, Proline Promass 84 HART • BA063D, Proline Promass 83 PROFIBBUS DP/PA • BA129D, Proline Promass 84 MODBUS RS485 • BA065D, Proline Promass 83 FOUNDATION Fieldbus • BA107D, Proline Promass 83 Modbus RS485 Contents General warnings .
  • Page 2: General Warnings

    IP 67, they shall be used. Alternatively Ex e cable glands specified or provided by Endress+Hauser Flowtec AG can be used. The cables must be installed in such a way, that they are fixed in place in order to ensure adequate strain relief.
  • Page 3: Coc Certificates Of Conformity

    The measuring system consists of transmitters and sensors. system Two versions are available: • Compact version: transmitters and sensors form a mechanical unit. • Remote version: transmitters and sensors are installed separately and connected to each other via a connecting cable. Endress+Hauser...
  • Page 4: Nameplates

    20 Fluid temperature range 21 Secondary containment pressure range 22 Density accuracy 23 Additional information, e.g. 5P-CAL = 5-point calibration, 3.1B = 3.1 B certificate for wetted material 24 Device nominal diameter 25 Nominal pressure 26 Direction of flow Endress+Hauser...
  • Page 5: Type Code

    , T1 Type (compact/remote; Item No. 14 in type code) Type Min. ambient temperature T a min A, L Compact –20 °C 1, 4, M, N –40 °C E, F, J, K Remote –20 °C 7, 8 –40 °C Endress+Hauser...
  • Page 6: Temperature Table Compact Version

    (350) Promass 8*F**-3*********** DN 80 Promass 8*F**-4*********** (85 °C) (100 °C) (135 °C) (200 °C) (300 °C) (450 °C) DN 8 +50 °C DN 15...50 Promass 8*H**-************ DN 8 (200) (200) +60 °C DN 15...50 160 (180) (200) (200) Endress+Hauser...
  • Page 7 The minimum medium temperature is –50 °C for Promass A/F/H/I/M/P/S, and –40 °C for Promass E. The minimum ambient temperature T for Promass 83/84 A/E/F/H/I/M/P/S is –20 °C. A version for ambient temperatures T up to –40 °C is optionally available. Endress+Hauser...
  • Page 8: Temperature Table Remote Version

    The remote version transmitter has a T6 temperature class rating when installed in the Ex d housing for operation at ambient temperatures up to T = 60 °C. The maximum ambient temperature range is –20 to +60 °C. A version for ambient temperatures T up to –40 °C is optionally available. Endress+Hauser...
  • Page 9: Gas And Dust Explosion Protection

    Transmitter housing on connection housing, remote version Sensor connection housing, remote version Screw terminal for connecting to the potential equalization Connection compartment cover Connecting cable remote version m and n see following section “Cable entries” Note! Connection of remote version connecting cable → Page 11 Endress+Hauser...
  • Page 10: Cable Entries

    3.1 Bus terminator PROFIBUS PA and FOUNDATION Fieldbus 3.2 Bus terminator PROFIBUS DP and MODBUS Bus supply unit or automation system 4a Potential equalization line is fed out into the safe area Note! The length of the spur must be observed. Endress+Hauser...
  • Page 11: Connection Of Remote Version Connecting Cable

    The connection of the remote version, between the sensor and the transmitter, has Ex i explosion protection. The maximum cable length between transmitter and sensor must not exceed 120 m. " Caution! Only preterminated connecting cables supplied by Endress+Hauser may be used. Endress+Hauser...
  • Page 12: Electrical Connection

    AC: U = 85 to 260 V; AC: U = 20 to 55 V Caution! DC: U = 16 to 62 V Observe the grounding plans Power consumption: 15 VA / 15 W of the system! Intrinsically safe circuit 260 V AC Endress+Hauser...
  • Page 13: Terminal Assignment And Connection Data For Signal Circuits

    Ex ia Safety-related – – – 30 V DC values 600 mA 8.5 W ≤ 10 μH ≤ 5 nF FISCO Field device Functional – – – galvanically isolated, values 9 to 32 V DC 12 mA IEC 61158-2 (MBP) Endress+Hauser...
  • Page 14 < 400 Ω Open Collector HART ≥ 250 Ω Full scale frequency 2 to 5000 Hz Permitted values in the event of simultaneous occurrence of concentrated inductances and capacitances. The interconnection must be assessed according to the valid construction provisions. Endress+Hauser...
  • Page 15 4 to 20 mA passive: 4 to 20 mA voltage drop ≤ 9 V voltage drop ≤ 9 V < [(V – 9 V) ÷ 25 mA] < [(V – 9 V) ÷ 25 mA] p. supply p. supply Endress+Hauser...
  • Page 16: Terminal Assignment And Connection Data For Signal Circuits (Energy Limited Circuits/Ex Nl/Non Incendive Field Wiring)

    Ex ia Safety-related – – – 35 V DC values 600 mA 8.5 W ≤ 10 μH ≤ 5 nF FNICO Field device Functional – – – galvanically isolated, values 9 to 32 V DC 12 mA IEC 61158-2 (MBP) Endress+Hauser...
  • Page 17: Terminal Assignment And Connection Data For Signal Circuits (Non-Intrinsically Safe Circuits)

    Relay output 2 Relay output 1 Status input 84***- *...*7 Safety-related and functional values of signal circuits → Page 18 * PROFIBUS DP, MODBUS RS485: – Terminal 26 (+) → B (RxD/TxD-P) – Terminal 27 (–) → A (RxD/TxD-N) Endress+Hauser...
  • Page 18 RS485 as per Standard EIA/TIA-485 Terminal 24: +5 V Terminal 25: DGND FOUNDATION Fieldbus galvanically isolated, = 9 to 32 V DC = 12 mA IEC 61158-2 (MBP) MODBUS RS485 galvanically isolated, RS485 as per Standard EIA/TIA-485 Endress+Hauser...
  • Page 19: Service Adapter

    Proline Promass 83, 84 NEPSI Zone 1, Zone 21 Service adapter The service adapter is only used for connecting service interfaces approved by Endress+Hauser. Warning! It is not permissible to connect the service adapter whilst the atmosphere is considered to be explosive.
  • Page 20 www.endress.com/worldwide XA122D/06/en/03.10 71111298 FM+SGML 6.0...