Setting And Adjustment; Selecting The Power Supply Of The Fans - Trane MERCURY EDAB 1105A Technical Manual

Mercury close control unit
Table of Contents

Advertisement

To shut down the unit carry out the following procedure:
WA R N I N G ! D u r i n g p ro l o n g e d b re a ks a
spontaneous migration of the refrigerant may
occur in the casing of the compressor, which
may cause foaming of the oil and consequent
damage because of the lack of lubrification. It is
recommended that the main switch is not turned
off during weekly breaks.
on the first screen of the user terminal, press keys A5
or A7 until the SWITCH OFF UNIT screen appears;
press the ENTER key to confirm;
the following icons will appear
Press the ENTER to confirm

SETTING AND ADJUSTMENT

Selecting the power supply of the fans

WARNING! Before establishing the electrical
connection, make sure that the power supply
is off. Also ensure that it is not possible to
reconnect the power during the operation.
WARNING! In the case of a unit with ducts, the
load loss from the exhaust duct must be less
than 100 Pa.
In the following table the voltage levels for each model
working in the standard version are given.
E*AB - E*WB: Air and water condensing direct expansion unit
Refrigerant: R410A
20 Pa
EU4
1105 - 1106
180
2107 - 2207 -
260
21 09 2209
2111 - 2211 - 2113 -
250
2213 - 2216 - 2218
2222 - 4222 -
270
2225 - 4225
2222A - 2242A -
230
2522A - 2542A
4228
240
SERIES
Model
Refrigerant
Air flow [m
/h]
3
Power supply voltage
[V]
230
250
260
270
280
290
300
310
320
340
360
380
400
PKG-SVX19B-E4
EU5
Post heating Post heating+ EU5
180
180
260
260
260
260
270
270
240
240
240
240
E*AB - E*WB
2107 - 2207
2111 - 2211
2109 - 2209
2113 - 2213
R410A
8180
11650
[Pa]
[Pa]
-
-
-
20
20
25
37
55
62
83
89
113
114
142
143
173
166
200
204
245
255
305
307
363
389
457
HOW TO ADJUST FAN SPEED
In the ED*B and EU*B units, the speed of the fan rotation can be
varied by using the ATR transformer (F1).
To obtain the required prevalence of the implant, it is possible
to vary the voltage by selecting one of the following levels:
Models 0511-0611
140V -160V -180V -190 - 200V -210V -220V -230V
Models 0721-1822
230V - 250V - 260V - 270V - 280V - 290V - 300V - 310V - 320V -
340V - 360V - 380V - 400V.
Models 2222 - 2242 - 2522 - 2542 - 2842 - 3342 : 150V - 180V
- 200V - 230V - 240V - 260V - 280V - 300V - 320V - 340V - 360V
- 380V - 400V.
In the following table the maximum pressure available (expressed in
Pa) for each voltage level of the transformer is indicated. The values
are given for the maximum air flow (expressed in m3/h).
Air flow [m
Power supply voltage
190
270
270
280
240
260
SERIES
2216 2218
Model
Refrigerant
5740
Air flow [m
Power supply voltage
[Pa]
-
-
-
20
36
65
124
125
153
196
256
315
403
F1
Model
/h]
3
Refrigerant
[V]
140
160
180
190
200
210
220
230
2222 - 4222
/h]
22000
3
[V]
[Pa]
150
-
180
-
200
-
230
20
240
54
260
145
280
193
300
236
320
275
340
309
360
338
380
362
400
369
E*AB - E*WB
1105 - 1106
5740
R410A
[Pa]
-
20
44
71
101
137
176
196
E*AB - E*WB
2225 - 4225
4228
R410A
23000
23500
[Pa]
[Pa]
-
-
-
-
-
-
-
-
20
-
111
20
155
88
197
129
235
163
265
195
295
222
320
295
327
305
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents