BACKFLOW LINE DIMENSIONING (LIQUID)

To avoid gas development inside the line and to ensure an
adequate pressure is reached inside the laminating unit,
the liquid line must be correctly dimensioned. Generally, the
systems are dimensioned so that pressure loss along the line
causes a variation of the saturation temperature between
0,5 K and 1 K
During the installation of the cooling unit, a solenoid
valve should be fitted on the liquid line between
the inner unit and the external condenser, to avoid
malfunctioning and to protect the compressor from
unwanted liquid migration during start- up.
Liquid line external diameters
1105
MODEL
R410A
16 mm
Remote air cooled condenser
MODEL
Number/
Suggested model (1) (2)
MODEL
Number/
Suggested model (1) (2)
MODEL
Number/
Suggested model (1) (2)
(1) With fan speed control
(2) External temperature = 35°C
26
1106
2107 - 2109
2110 - 2113
1 x
1 x
16 mm
16 mm
1105
1 x
CAP0661
2111
1 x
CAP1301
2222
1 x
CAP2002
EDA* - EUA*
2207 - 2209
2211 - 2213
1 x
2 x
16 mm
EDA* - EUA*
1106
2107
1 x
1 x
CAP0661
CAP0801
2211
1113
2 x
1 x
CAP0511
CAP1301
EDA* - EUA*
4222
1 x
CAP2002
2213 - 2216
2222
2218
4222
2 x
2 x
16 mm
18 mm
2207
2 x
CAP0331
CAP1011
EDA* - EUA*
2213
1 x
CAP1802
2 x
CAP0661
2225
4225
1 x
2 x
CAP3002
CAP3002
2225
-
4225
4228
2 x
2 x
18 mm
22 mm
2109
2209
1 x
2 x
CAP0361
2216
2218
1 x
1 x
CAP2002
CAP3002
2 x
2 x
CAP0801
CAP1011
4228
1 x
CAP4002
PKG-SVX19B-E4