Operating Description - Trane MERCURY EDAB 1105A Technical Manual

Mercury close control unit
Table of Contents

Advertisement

CHILLED WATER UNITS WITH EC BACKWARD CURVED BLADE FANS
Model EDCV - EUCV
Height
Width
Depth
Weight
Chilled water flow (*)
Chilled water flow (**)
Electric supply voltage
Model EDCV
Height
Width
Depth
Weight (Complete version) (1)
Chilled water flow (*)
Chilled water flow (**)
Electric supply voltage
(*) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 7/12°C, ethylene glycol 0%
(**) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 10/15°C, ethylene glycol 0%

Operating description

CW CHILLED WATER UNITS
The CW uses the availability of chilled water to control the
room conditions.
This version of MERCURY has a relatively simple construction
and gives outstanding reliability.
The microprocessor controls the modulating action of the 3
way (or optional 2 way) chilled water valve to give accurate
control.
Careful sizing of the heat exchanger coils allows a high
sensible to total cooling ratio under most operating
conditions.
42
0070
0100
mm
1960
1960
mm
1010
1310
mm
750
865
kg
280
306
l/h
4690
5750
l/h
3380
4420
V
400V/3ph+N/50Hz
0270
mm
1960
mm
2170
mm
865
kg
502
l/h
16887
l/h
13063
V
400V/3ph+N/50Hz
0120
0170
1960
1960
1310
1721
865
865
314
395
7270
9210
11950 15230
4990
6060
0340
0400
1960
1960
2580
2580
865
865
720
740
19000
21680
14675
16059
PKG-SVX19B-E4
0200
0250
1960
1960
2172
2172
865
865
443
458
8240 10740

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents