Vent Pipe Installation - Slant/Fin Q3-4 Supplemental Instructions

High efficiency oil-fired hot water boiler
Table of Contents

Advertisement

Available languages

Available languages

!
WARNING
Improper installation, adjustment, alteration, service or
maintenance could result in death or serious injury. Do
not enclose vent. Do not use barometric draft regulator.
Do not route vent through walls, floors or ceilings.
Venting and vent terminal are dedicated to the Boiler
only; do not attempt to vent any other appliance
through it.
Barometric draft regulator (furnished with standard
chimney vent boiler) is not used for direct venting.
Flexible Vent Installation
Supplied flexible exhaust duct is a double wall, one (1) inch
clearance to combustibles, flexible venting material.
Inner pipe is constructed of 4 inch inside diameter 316
stainless steel, with two-ply aluminum outer pipe.
High temperature insulation separates inner and outer flex
pipes.
Vent installation shall conform to requirements of authority
having jurisdiction or in absence of such requirements NFPA
31 Installation Of Oil Burning Equipment (U.S.) or CSA
B139 (Canada) and applicable provisions of local building
codes and these instructions.
!
CAUTION
Use appropriate safety precautions. Thin metal
edges are extremely sharp. If not avoided, could
result in minor or moderate injury.
1.
In as short and straight a run as possible without any
unnecessary bends.
2.
No dips or sags throughout full length of vent.
3.
Slope vent upwards from appliance at least 1/4" per
foot.
4.
Do not bend vent more than 90°.
5.
May cut vent to minimum of 5 feet in length using fine
tooth (24 teeth per inch) hacksaw blade.
6.
Clean male and female ends of appliance adapter
and terminal adapter with residue free brake cleaner
solvent.
7.
Apply minimum 1/4" bead of Si-Ultra Copper Sealant
(provided) onto outside of male end of appliance
adapter. Fit adapter to vent by threading it counter
clockwise until it stops. Insure joint is not cross
threaded. Tighten gear clamp (where provided) on
outer cover. See figures 6 and 7.

VENT PIPE INSTALLATION

Figure 5 - Appliance Connector w/ Test Port
Figure 6 - Male End
Figure 7 - Flex Vent Assembly Detail
5
P/N 473921000