Slant/Fin Q3-4 Supplemental Instructions

High efficiency oil-fired hot water boiler
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Direct Venting Of Oil Fired Boilers ..................................................................................... 2
Vent Terminal Locations ................................................................................................... 3
Vent Terminal Installation ................................................................................................ 4
Intake Air Pipe Installation ............................................................................................... 4
Vent Pipe Installation ...................................................................................................... 5
Vent Pipe Installation ...................................................................................................... 6
Blocked Vent Safety Shutoff System .................................................................................. 7
Sequence Of Operation ................................................................................................... 8
Final Check Out .............................................................................................................. 9
Burner Settings Tables .................................................................................................. 10
Wiring Diagrams ........................................................................................................... 11
Operation And Troubleshooting ....................................................................................... 12
French Manual.....................................................................................................15
SUPPLEMENTAL INSTRUCTIONS:
DIRECT VENT
INSTRUCTIONS FOR HIGH EFFICIENCY OIL-FIRED
HOT WATER BOILER
!
Installations of venting shall be done only by a
qualified expert and in accordance with these
instructions. Venting a boiler or any other oil
appliance with improper methods or materials may
result in serious injury or death due to fire or to
asphyxiation from poisonous gases such as carbon
monoxide which is odorless and invisible.
Keep area around vent terminal free of snow, ice, and
debris.
Information contained in this manual pertains to direct vent
boilers equipped with manufacturer installed blocked vent
safety control system (pressure switch).
WARNING
P/N 473921000
[240011797, Rev. D 06/07/2018]

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin Q3-4

  • Page 1: Table Of Contents

    SUPPLEMENTAL INSTRUCTIONS: DIRECT VENT INSTRUCTIONS FOR HIGH EFFICIENCY OIL-FIRED HOT WATER BOILER Information contained in this manual pertains to direct vent boilers equipped with manufacturer installed blocked vent safety control system (pressure switch). WARNING Installations of venting shall be done only by a qualified expert and in accordance with these instructions.
  • Page 2: Direct Venting Of Oil Fired Boilers

    DIRECT VENTING OF OIL FIRED BOILERS Introduction F. Less than 1 foot (0.3m) above grade level within 6 feet (1.80m) of any combustion air inlet, unless • Direct Vent refers to sealed combustion system. appliance is otherwise certified. • Draft regulator (furnished with standard chimney vent G.
  • Page 3: Vent Terminal Locations

    VENT TERMINAL LOCATIONS Figure 2 - Vent Terminal Locations (Canada) Figure 3 - Vent Terminal Location (USA) P/N 473921000...
  • Page 4: Vent Terminal Installation

    VENT TERMINAL INSTALLATION Vent Terminal Location See table 1 for equipment certified for use with this Figure 4 - Inside View of Vent Terminal appliance. Select location of wall penetration that conforms to code for exterior location: As close to appliance as possible, Maintains clearance to combustibles, Maintains minimum 1/4 inch per foot slope back to appliance.
  • Page 5: Vent Pipe Installation

    VENT PIPE INSTALLATION Figure 5 - Appliance Connector w/ Test Port WARNING Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury. Do not enclose vent. Do not use barometric draft regulator. Do not route vent through walls, floors or ceilings. Venting and vent terminal are dedicated to the Boiler only;...
  • Page 6: Vent Pipe Installation

    VENT PIPE INSTALLATION Sheet metal transition ring on boiler flue collar is only Figure 8 - Female End used for chimney venting. It is not used for direct venting. The transition ring must be removed from the boiler’s cast iron flue collar before installing the appliance adapter onto the flue collar.
  • Page 7: Blocked Vent Safety Shutoff System

    BLOCKED VENT SAFETY SHUTOFF SYSTEM Blocked Vent Safety Shut Off System (BVS) Riello 40BF Burner: Oil burners used with this direct vent boiler are equipped Refer to Figure 9. Check initial air shutter and head with a Blocked Vent Safety shutoff system (BVS) utilizing settings.
  • Page 8: Sequence Of Operation

    SEQUENCE OF OPERATION Riello 40BF Figure 9 - Air Shutter Setting Room temperature drops, thermostat calls for heat. Pre-purge begins, lasting 5 to 15 seconds. BVS is energized. If flue is clear, pressure switch allows ignition sequence to continue. Oil Solenoid opens allowing oil to reach burner electrodes.
  • Page 9: Final Check Out

    FINAL CHECK OUT Final Check Out: • Carefully examine complete vent system for leaks. This may be done by spraying soapy solution on all joints and watching for bubbles during pre-purge. The hot vent can be checked with lit taper for signs of air movement around joints or seams.
  • Page 10: Burner Settings Tables

    BURNER SETTINGS TABLES Table 1: THIS HIGH EFFICIENCY BOILER IS CERTIFIED FOR USE AS DIRECT VENT BOILER ONLY WITH THE FOLLOWING PART NUMBERS Boiler Model: Q3-4 Q3-5 Q3-6 Oil Burner - Riello 40BF 473024000 473025000 473026000 Vent Terminal 473110000 Venting Kit 4" x 15 Feet...
  • Page 11: Wiring Diagrams

    WIRING DIAGRAMS Figure 10 - Riello Wiring Diagram With Post Purge Timer And Blocked Flue Pressure Switch Safety If a neutral or ground lead is attached to terminal 4, the CONTROL BOX on the burner will be damaged should lockout occur. P/N 473921000...
  • Page 12: Operation And Troubleshooting

    OPERATION AND TROUBLESHOOTING Riello 40BF blocked vent safety (BVS) Operation External Action Appliance Response • Burner enters pre-purge. • After pre-purge, oil valve is energized and burner lights off. Thermostat calls for heat. • Burner operates in run mode. • Normally closed pressure switch monitors for vent or combustion air intake blockage. •...
  • Page 13 OPERATION AND TROUBLESHOOTING RIELLO 40BF Blocked Vent safety system (BVS) TROUBLESHOOTING Condition: Thermostat is calling for heat. Burner is not running. Problem Possible Cause Remedy Contacts closed. Go to step #2. Verify pressure tubing is connected properly and clear of obstructions. Test BVS pressure switch contacts Verify vent is not obstructed.
  • Page 14 HOMEOWNER’S REFERENCE TABLE Model No. Serial No. Date Installed Contractor Contact Address Postal Code Telephone No. After Hours No. SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 FAX: (516) 484-0933 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario P/N 473921000...
  • Page 15: French Manual

    DIRECTIVES SUPPLÉMENTAIRES : VENTILATION DIRECTE DIRECTIVES POUR LES CHAUDIÈRES À MAZOUT À HAUTE EFFICACITÉ CHAUDIÈRE À EAU CHAUDE Les renseignements fournis dans ce manuel se rapportent aux chaudières à évacuation directe dotées d’un dispositif de sécurité en cas d’obstruction de l’évacuation (interrupteur manométrique) installé...
  • Page 16: Évacuation Directe De Chaudières À Mazout

    ÉVACUATION DIRECTE DE CHAUDIÈRES À MAZOUT Introduction Moins de 1 pi (0,3 m) au-dessus du sol à moins de 6 pi (1,80 m) de toute entrée d’air de combustion, à moins • Le terme « évacuation directe » se rapporte à un système de d’une certification différente.
  • Page 17: Emplacement Des Extrémités D'évent

    EMPLACEMENT DES EXTRÉMITÉS D’ÉVENT Figure 2 – Emplacements des extrémités d’évent (Canada) Entrée d’air soufflé Figure 3 – Emplacements des extrémités d’évent (É.-U.) Moins de 10 pi (3 m).Entrée d’air soufflé. Min. 4 pi (1,2 m). Extrémité. Min. 3 pi (1 m). Entrée d’air soufflé.
  • Page 18: Installation Des Extrémités D'évent

    INSTALLATION DES EXTRÉMITÉS D’ÉVENT Emplacement des extrémités d’évent Figure 4 – Vue intérieure de l’extrémité de l’évent Consulter le tableau 1 pour l’équipement homologué pour une utilisation avec cet appareil. Choisir un emplacement pour passe-mur conforme au code se rapportant à l’emplacement extérieur : Le plus près possible de l’appareil Qui conserve un dégagement par rapport aux matériaux inflammables,...
  • Page 19: Installation Du Tuyau D'évent

    INSTALLATION DU TUYAU D’ÉVENT Installation de l’évent – évacuation directe Figure 5 – Raccord d’appareil avec orifice de test MISE EN GARDE L’installation, le réglage, la modification, la réparation ou l’entretien inadéquats pourraient entraîner la mort ou des blessures graves. Ne pas installer l’évent dans un espace confiné. Ne pas diriger le conduit d’évent à...
  • Page 20 INSTALLATION DU TUYAU D’ÉVENT Anneau de transition en tôle sur buse de chaudière est Figure 8 – Extrémité femelle uniquement utilisé pour la ventilation de cheminée. Il n’est pas utilisé pour l’évacuation directe. L’anneau de transition doit être retiré de la chaudière en fonte avant d’installer la buse de l’appareil l’adaptateur sur la buse.
  • Page 21: Dispositif De Sécurité En Cas D'obstruction De L'évacuation

    DISPOSITIF DE SÉCURITÉ EN CAS D’OBSTRUCTION DE L’ÉVACUATION Dispositif de sécurité en cas d’obstruction de Brûleur Riello 40BF : l’évacuation (BVS) Consulter la figure 10. Vérifier le réglage initial du clapet d’arrivée d’air et du régulateur. Retirer le couvercle du brûleur et Brûleurs à...
  • Page 22: Séquence De Fonctionnement

    SÉQUENCE DE FONCTIONNEMENT Riello 40BF Figure 9 – Réglage du clapet d’air La température de la pièce chute, le thermostat demande de la chaleur. Le prébalayage de 5 à 15 secondes commence. Le BVS est mis sous tension. Si le tuyau d’évacuation n’est pas obstrué, l’interrupteur manométrique permettra à...
  • Page 23: Vérification Finale

    VÉRIFICATION FINALE • Examiner attentivement le système d’évacuation pour repérer toute fuite. Pour ce faire, vaporiser une solution savonneuse sur tous les joints et surveiller la formation de bulles durant le prébalayage. On peut vérifier l’évent chaud à l’aide d’une bougie allumée pour repérer des signes de courants d’air autour des joints ou raccords.
  • Page 24: Tableaux De Réglage Du Brûleur

    TABLEAUX DE RÉGLAGE DU BRÛLEUR Tableau 1 : CETTE CHAUDIÈRE À HAUT RENDEMENT EST CERTIFIÉ POUR UTILISATION EN TANT QUE Chaudière à évacuation directe qu'avec les références suivantes Modèle de chaudière: Q3-4 Q3-5 Q3-6 Brûleur à huile - Riello 40BF 473024000...
  • Page 25: Schémas Du Circuit Électrique

    SCHÉMAS DU CIRCUIT ÉLECTRIQUE Figure 10 – Schéma du circuit électrique du Riello avec une minuterie postbalayage et un dispositif de sécurité en cas d’obstruction de l’évent L’interrupteur de sécurité de la BOÎTE DE COMMANDE 530SE est doté d’un contact permettant la téléobservation d’un dérangement du brûleur.
  • Page 26: Fonctionnement Et Guide De Dépannage

    FONCTIONNEMENT ET GUIDE DE DÉPANNAGE Fonctionnement du dispositif de sécurité en cas d’obstruction de l’évacuation (BVS) Riello 40BF Action externe Réaction de l’appareil • Le brûleur entre en mode de prébalayage. • Après le prébalayage, la soupape à mazout est mise sous tension et le brûleur s’éteint. Le thermostat demande de la chaleur.
  • Page 27 FONCTIONNEMENT ET GUIDE DE DÉPANNAGE GUIDE DE DÉPANNAGE du dispositif de sécurité en cas d’obstruction de l’évent (BVS) RIELLO 40BF Manifestation : Le thermostat demande de la chaleur. Le brûleur ne fonctionne pas. Problème Cause possible Solution Contacts fermés. Passer à l’étape 2. Vérifier si les canalisations sous pression sont bien raccordées et qu’elles ne sont Tester les contacts de l’interrupteur pas obstruées.
  • Page 28 TABLEAU DE RÉFÉRENCE DU PROPRIÉTAIRE Nº de modèle Nº de série Date d’installation Installateur Contact Adresse Code postal Nº de téléphone Nº d’urgence SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 FAX: (516) 484-0933 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario...