Johnson Controls IOM1711 Installation Manual

Johnson Controls IOM1711 Installation Manual

Hide thumbs Also See for IOM1711:

Advertisement

Quick Links

Application
The IOM1711 and IOM2711 input/output expansion
modules are part of the Metasys
Equipment Controller family. Input/Output Module
(IOM) expansion modules expand the number of
I/O points connected to a Network Automation
Engine (NAE), Network Control Engine (NCE), Field
Equipment Controller (FEC), VAV Modular Assembly
(VMA), or Advanced Application Field Equipment
Controller (FAC) to monitor and control a wide
variety of HVAC equipment.
IOM field controllers operate on an RS-485 BACnet
MS/TP Bus and integrate into Johnson Controls
and third-party BACnet systems.
Important: In Metasys system smoke control
applications, use only the MS-IOM171x-0U and
MS-IOM271x-0U at Metasys Release 8.1 that
are UL 864 UUKL/UUKLC 10th Edition Smoke
Control Listed. For Metasys system smoke
control applications, you must refer to the
Metasys System UL 864 UUKL Tenth Edition Smoke
Control System Technical Bulletin (LIT-12012487)
for detailed requirements and procedures
for installing, commissioning, and operating
UL 864 UUKL/UUKLC Listed Metasys system
devices. The UL 864 UUKL/UUKLC listing for
Smoke Control Equipment is voided if (1) you
do not use the required software tools at the
required versions; or (2) you do not meet the
requirements or do not follow the procedures
as documented in the Metasys System UL
864 UUKL Tenth Edition Smoke Control System
Technical Bulletin (LIT-12012487).
Note: At Controller Configuration Tool (CCT)
Release 10.1 and later, a new capability was
introduced allowing VMAs, FECs, and FACs
to communicate by using either the BACnet
or the N2 field bus networking protocol. The
operation of the IOM Input/Output Module
is not affected by the selection of the BACnet
or the N2 protocol in the host controller when
the IOM is connected to the host controller
using the SA bus. Only the BACnet protocol is
supported when the IOM is connected directly
to the trunk using the FC bus.
IOM1711 and IOM2711 Input/Output Module
system Field
®
®
®
Installation Guide
North American Emissions
Compliance
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment
is operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
Installation
Observe these guidelines when installing a field
controller:
• Transport the controller in the original container
to minimize vibration and shock damage.
• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical
shock.
Parts Included
• One controller with removable terminal blocks
(Power and SA/FC bus are removable)
Part No. 24-10144-76 Rev. P
2019-10-18
*241014476P*
(barcode for factory use only)
MS-IOM1711-x, MS-IOM2711-x

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls IOM1711

  • Page 1 Installation Guide Part No. 24-10144-76 Rev. P 2019-10-18 Application North American Emissions Compliance The IOM1711 and IOM2711 input/output expansion modules are part of the Metasys system Field ® Canada Equipment Controller family. Input/Output Module (IOM) expansion modules expand the number of...
  • Page 2: Materials And Special Tools Needed

    • One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only) • Small straight-blade screwdriver for securing wires in the terminal blocks IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 3 Universal Inputs (UI) Terminal Blocks (Not available on IOM17). See Table 2 for more information. bottom, and front of the controller). Relay Output Terminal Blocks (Not available on IOM17). See Table 2 for more information. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 4: Wall Mount Applications

    Hang the controller on the DIN rail by the hooks at the top of the (DIN rail) channel on the back of the controller (Figure 3), and position the controller snugly against the DIN rail. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 5: Terminal Blocks And Bus Ports

    Input and Output terminal blocks Most of the input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller. See IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 6: Sa/Fc Bus Terminal Block

    Control applications. It is not required for applications in North America. To install the ferrite ring, pass the two 24 VAC supply powerwires through the opening of the ring and then complete five wraps or turns of IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 7: Wireless Network Applications

    Wireless Field Bus system, refer to the manufacturers. Refer to the transformer ZFR1800 Series Wireless Field Bus System manufacturer’s instructions and the project Product Bulletin (LIT-12011336). installation drawings for wiring details. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 8 • Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software setup. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 9 Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel See Guideline A in Table 3. [ Johnson Controls sensor], 1k Platinum, and A99B Silicon Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type II)
  • Page 10: Cable And Wire Length Guidelines

    Cable and wire length guidelines Cable length guidelines for recommended wire size Table 3 defines cable length guidelines for the various wire sizes that may be used for wiring low- voltage (<30 V) input and outputs. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 11: Maximum Cable Length Versus Load Current

    (<30 V) Inputs and Outputs by current and wire • Refer to the MS/TP Communications Bus Size Technical Bulletin (LIT-12011034) for detailed information regarding wire size and cable length requirements for the SA and FC buses. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 12 See Table 3 to determine wire size and cable lengths for cables. Note: The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034). IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 13: Termination Details

    Type of field device Termination diagrams Output Temperature Sensor Voltage Input - External Source Voltage Input - Internal Source Voltage Input (Self- Powered) Current Input - External Source (Isolated) Current Input -Internal Source (2-wire) IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 14 Source (in Loop) Feedback from EPP-1000 Dry Contact UI or BI Incremental Control to Actuator (Switch Low, External Source) 24 VAC Binary Output (Switch Low, Externally Sourced) 24 VAC Binary Output (Switch High, Externally Sourced) IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 15 Termination diagrams Output Incremental Control to Actuator (Switch High, Externally Sourced) Analog Output (Current) 4-20 mA Output to Actuator Voltage (Analog Output) 4-20 mA Output to Actuator) 0-10 VDC Output to Actuator (Internal Source) IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 16: Setup And Adjustments

    Set switch 128 to ON for wireless FC To set the device addresses on Metasys field bus applications only. controllers: Set all of the switches on the address DIP switch block (128 through 1) to Off. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 17: Removing The Controller Cover

    Write each controller's device address on the white label below the DIP switch block on the The controller cover is held in place by four controller's cover. plastic latches that extend from the base and IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 18: Cover Removed Eol Switch

    Each controller has an EOL switch, which, when set to ON, sets the controller as a terminating device on the bus. See Figure 11 for the EOL switch location. The default EOL switch position is Off. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 19: Troubleshooting The Controllers

    Off Steady = EOL switch in Off position devices) Repair information If a controller fails to operate within its specifications, replace the controller. For a replacement controller, contact your Johnson Controls representative. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 20 Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653) for specific sensor WRZ Series Wireless Room Sensors model descriptions. Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the appropriate Mobile Access Portal (MAP)Gateway product for your region. IOM1711 and IOM2711 Input/Output Module Installation Guide...
  • Page 21: Technical Specifications

    24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2 Supply Voltage (North America), Safety Extra-Low Voltage (SELV) (Europe) 14 VA maximum for IOM1711 or IOM2711 only Note: VA rating does not include any power supplied to the peripheral devices Power Consumption connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can consume up to 12 VA for each BO or CO;...
  • Page 22: Product Warranty