Siemens FDM243H Technical Manual
Siemens FDM243H Technical Manual

Siemens FDM243H Technical Manual

Manual call point
Hide thumbs Also See for FDM243H:

Advertisement

Quick Links

FDM243H
Manual call point
Technical Manual
A6V10374021_c_en_--
2014-07-01
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDM243H

  • Page 1 FDM243H Manual call point Technical Manual Building Technologies A6V10374021_c_en_-- 2014-07-01 Control Products and Systems...
  • Page 2 Legal notice Technical specifications and availability subject to change without notice. © 2013 - 2014 Copyright by Siemens Switzerland Ltd Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited.
  • Page 3: Table Of Contents

    Table of contents About this document ..................5 Applicable documents ..................6 Technical terms ....................6 History of changes ....................7 Safety ......................8 Safety instructions ....................8 Safety regulations for the method of operation ..........10 Standards and directives complied with ............12 Release Notes ....................12 Structure and function .................
  • Page 4 Maintenance / Repair ..................33 Resetting after an alarm ................. 33 Status query ....................34 Function check ....................34 Replacing the glass insert ................35 Specification ....................37 Technical data ....................37 Dimensions ....................38 Master gauge for recesses ................39 Environmental compatibility and disposal ............
  • Page 5: About This Document

    About this document Applicable documents 1 About this document Goal and purpose This document contains all information on the manual call point FDM243H. Following the instructions consistently will ensure that the product can be used safely and without any problems. Target groups...
  • Page 6: Applicable Documents

    Troubleshooting A6V10211076 Operation Manual Fire control panel / Fire terminal FC72x / FT724 A6V10229261 List of compatibility (for 'Cerberus™ PRO' product line) A6V10356927 Data sheet Manual call point FDM243H A6V10374023 Installation Manual call point FDM243H 1.2 Technical terms Term Explanation...
  • Page 7: History Of Changes

    About this document History of changes 1.3 History of changes The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
  • Page 8: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger...
  • Page 9 Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
  • Page 10: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, assembly, installation,...
  • Page 11 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 12: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 13: Structure And Function

    Indication of the condition (Alarm, localization or test) by means of a dichromatic LED Integrated line separation function Communication via FDnet/C-NET Sturdy housing for use outdoors and in humid areas Manual call point FDM243H Building Technologies A6V10374021_c_en_-- Fire Safety 2014-07-01...
  • Page 14: Details For Ordering

    Structure and function Overview 3.1.1 Details for ordering Manual call point FDM243H: Type Order no. Designation FDM243H S54311-F8-A1 Manual call point Scope of delivery: Red housing with glass insert and switching unit 1 key 1 V-pin M20 x 1.5 2 screws...
  • Page 15: Product Version Es

    Structure and function Overview 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number. You will find the details of your device's product version: On the packaging label On the product label or the type plate Product version on the packaging label...
  • Page 16: Setup

    3.2 Setup 3.2.1 Manual call point The manual call point FDM243H triggers an alarm when the glass insert is pushed in and the alarm button is pressed (indirect activation). The alarm is immediately transmitted to the control panel. When the alarm is activated, the switching unit must be reset and a new glass insert installed.
  • Page 17: Connections

    Structure and function Setup 3.2.2 Connections The manual call point has eight spring clips on the rear of the switching unit; these are for the detector line and for connecting external alarm indicators. Spring clips on the rear of the switching unit 3.2.3 Indication elements An LED is built into the switching unit as an internal alarm indicator.
  • Page 18: Function

    Structure and function Function 3.3 Function 3.3.1 Danger levels The manual call point can transmit the following danger levels to the control panel: Danger level Meaning Normal state, no danger Alarm Door status Danger level Meaning Door closed Door open The evaluation of the danger level and the resulting measures (e.g.
  • Page 19: Test Mode On The Manual Call Point

    Structure and function Function 3.3.4 Test mode on the manual call point You can activate test mode in the fire control panel by opening the door, and deactivate it by closing the door again. The test mode is only active for a short time and is indicated by the green LED.
  • Page 20: Diagnosis Levels

    Structure and function Function 3.3.5 Diagnosis levels The manual call point monitors its operation largely autonomously. The following diagnosis levels are derived from the different control measurements: Normal, no fault is present Replacement necessary Fault present When an error occurs which impairs the correct functionality of the device, a fault message is reported to the control panel.
  • Page 21: Accessories

    3.4 Accessories 3.4.1 Glass insert FDMG298 For alarm activation and protection against soiling Compatible with: – Manual call point FDM243H Order no.: S54311-B8-A1 3.4.2 Key FDMK294 Plastic key For opening doors on manual call points To help with resetting the alarm button Compatible with: –...
  • Page 22: Planning

    Planning Compatibility 4 Planning 4.1 Compatibility Compatible with control panels that support the FDnet/C-NET detector line. Detector line Control panel FC20xx FC72x SIGMASYS AlgoRex FDnet – – C-NET – – – X = compatible – = not compatible You will find details in the 'List of compatibility'. 4.2 Fields of application The manual call points are intended for use in places where a fire can be detected by people who can manually trigger an alarm.
  • Page 23: Mounting/Installation

    Commissioning Environmental influences 5 Mounting/Installation The manual call point is mounted and installed in three steps: 1. Preparation (see the chapter 'Preparation') 2. Installation (see the chapter 'Installation') 3. Electrical connection (see the chapter 'Installation') Building Technologies A6V10374021_c_en_-- Fire Safety 2014-07-01...
  • Page 24: Preparation

    Commissioning Preparation 5.1 Preparation For manual call point FDM243H, the surface-mounted cables are fed into the housing from below. Switching unit Keyhole cover V-pin Allen head screws Screwed cable gland Fastening material and an Allen key SW 3.0 are available.
  • Page 25: Installation

    2. Pull the cables through the entry opening(s) into the housing. 3. Tighten the cable gland so that it is properly sealed. The manual call point is now prepared for electrical connection. Screw holes for manual call point FDM243H Building Technologies A6V10374021_c_en_--...
  • Page 26: Installation

    Commissioning Installation 5.3 Installation Notes on work on electrical installations CAUTION Electrical voltage on lines Risk of injury due to electric shock During mounting and installation work, electrical voltage must not be applied to the lines. WARNING Deactivating the manual call points prevents alarms from being forwarded. Alarming does not take place.
  • Page 27 LINE Ext. AI SHIELD Connection diagram for manual call point FDM243H Connecting the manual call point The manual call point has eight spring clips on the rear of the switching unit; these are for the detector line and for connecting external alarm indicators.
  • Page 28 Commissioning Installation 5. Connect the switching unit to the housing by tightening the four Allen head screws (2) firmly. Check whether the button is protruding by about 3 mm. If the alarm button is pressed in, reset it. See the 'Checking function [ 29]' chapter 6.
  • Page 29: Commissioning

    Commissioning Localization and device testing 6 Commissioning The device is commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete. 6.1 Localization and device testing The manual call points have an internal alarm indicator. This internal alarm indicator may also be activated from the control panel for localization and device testing.
  • Page 30: Checking Function

    Commissioning Checking function 6.2 Checking function Checking is usually performed from the fire control panel, but it may also be performed from the manual call point. Resetting manual call point FDM243H Stopping lever for resetting Building Technologies A6V10374021_c_en_-- Fire Safety...
  • Page 31 Commissioning Checking function Checking from the fire control panel The manual call point is installed and electrically connected. See the chapter 'Installation [ 25]'. 1. Set the detector line to 'Test' on the fire control panel. The LED flashes green; this means the detector is in test mode. 2.
  • Page 32 Commissioning Checking function Enabling on FC72x fire control panels 1. In the main menu, select the 'Functions' menu item. The 'Functions' window is open. 2. Select 'Maintenance' and confirm with <ok>. A list of all element categories on which a command of the 'Maintenance' command group can be executed is indicated.
  • Page 33: Maintenance / Repair

    Maintenance / Repair Resetting after an alarm 7 Maintenance / Repair 7.1 Resetting after an alarm After an alarm is activated, the manual call point must be reset to a state in which it is ready for operation. Reset the detector to a state of operational readiness as follows: The glass insert has been shattered and the alarm button is pressed.
  • Page 34: Status Query

    Maintenance / Repair Status query 7.2 Status query Status query on the control panel Depending on the authorization level of the user and the control panel type, different actions can be performed from the control panel. Observe the notices in the control panel documentation. Document 009052 applies to fire control panels FC20xx.
  • Page 35: Replacing The Glass Insert

    Maintenance / Repair Replacing the glass insert 7.4 Replacing the glass insert The glass insert is square-shaped and can be inserted in any direction. Replace the glass insert as follows: The door (1) of the manual call point is open. See the chapter 'Preparation 23]'.
  • Page 36 Maintenance / Repair Replacing the glass insert Resetting the alarm button The alarm button is pressed. The door is open. Place the key (1) onto the round guide and turn it clockwise so that the black stopping lever (2) is pushed downward. The switching unit clicks and the alarm button is now protruding by approx.
  • Page 37: Specification

    Specification Technical data 8 Specification You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: A6V10356927 See also Applicable documents [ 8.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s);...
  • Page 38: Dimensions

    Specification Dimensions Connections Detector line and external alarm indicators: Spring clips Design Spring clips Cable cross section 0.2…1.5 mm² Screwed cable gland 2x M20 x 1.5 Cables Ø 6…12 mm Ambient conditions Operating temperature -35…+70 °C Storage temperature -40…+70 °C Air humidity (no moisture condensation) 95 % rel.
  • Page 39: Master Gauge For Recesses

    Specification Master gauge for recesses 8.3 Master gauge for recesses 8.4 Environmental compatibility and disposal This device is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: Use of reusable materials Use of halogen-free plastics...
  • Page 40: Index

    Index Index Impact Alarm button Chemicals, 22 Resetting, 36 Moisture, 22 Alarm indicator, 18, 29 Temperature, 22 Application area Internal alarm indicator, 18, 29 Ambient conditions, 22 Approvals, 37, 37 Line separator Function, 18 CE marking, 37, 37 List of compatibility, 6, 20, 22 Collective behavior Degraded mode operation, 20 Compatibility, 22...
  • Page 41 Index Building Technologies A6V10374021_c_en_-- Fire Safety 2014-07-01...
  • Page 42 Issued by © 2013-2014 Copyright Siemens Switzerland Ltd Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID...