Graco Reactor E-10 Instructions-Parts List Manual page 17

Plural component proportioner
Hide thumbs Also See for Reactor E-10:
Table of Contents

Advertisement

Model
120 V, 1 phase, 50/60 Hz, two 15 ft
(4.5 m) power cords, Heated
240 V, 1 phase, 50/60 Hz, two 15 ft
(4.5 m) power cords, Heated
240 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Heated
120 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Nonheated
240 V, 1 phase, 50/60 Hz, one 15 ft
(4.5 m) power cord, Nonheated
Model
Nonheated and two cord heated
models
Single cord heated model
NOTE: Cords must be 3-conductor grounded, rated for your environment.
To avoid electric shock, always unplug both cords
before servicing Reactor E-10.
1
Ensure no other high amp loads are connected
while running Reactor E-10.
2
To verify separate circuits, plug in Reactor E-10
or a worklight and cycle breakers on and off.
F
. 5 Use Two Separate Circuits for Two Cord Models
IG
311075ZAB
Table 2: Electrical Requirements
Required Power Source
Two separate, dedicated circuits
rated at minimum of 15 A each
Two separate, dedicated circuits
rated at minimum of 10 A each
Single dedicated circuit rated at
minimum of 16 A
Single dedicated circuit rated at
minimum of 15 A
Single dedicated circuit rated at
minimum of 8 A
Table 3: Extension Cord Requirements
1
Heater Power
Motor Power
Power Cord Connector
Required Wire Size
Up to 50 ft (15 m)
AWG 14
AWG 12
Two NEMA 5-15T
Two IEC 320, with two
local adapters:
Euro CEE74 Adapter
Australia/China Adapter
One NEMA 6-20P
One NEMA 5-15T
One NEMA 6-20P
Up to 100 ft (30 m)
AWG 12
AWG 10
2
1
Installation
TI7061a
17