3. Increase the protection from high-frequency radiation through shielded connecting cables.
– Lead the shielded connecting cables through the cable glands
– Connect the cable shield to the screw of the ground terminal
The screw of the ground terminal is electrically connected to the external protective
conductor connection.
4. Connect the input terminals
Connecting TH420 (Page 81)
Figure 6-4
5. Insert the temperature transmitter and screw it into place.
6. Insert the local display.
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
- or -
HART communication resistor
6.7 Connecting the SITRANS TF single chamber housing
④
and output terminals
⑥
(optional)
②
.
③
.
⑤
.
Connecting
93