Technical data
12.2 SITRANS TH320/TH420/TR320/TR420/TF320/TF420
FM/CSA
Name
Output terminals
SITRANS TH/
SITRANS TF single
chamber housing: 1, 2
SITRANS TR: 3, 4
SITRANS TF dual cham‐
ber housing: (+) and
(-)
Permissible ambi‐
ent temperature
Output terminals
SITRANS TH/
SITRANS TF single
chamber housing: 1, 2
SITRANS TR: 3, 4
SITRANS TF dual cham‐
ber housing: (+) and
(-)
Permissible ambi‐
ent temperature
Explosion protection
"Flameproof enclo‐
sure XP", "Dust igni‐
tion proof DIP" or "In‐
trinsic safety IS".
212
SITRANS TH/TR
NI, CL I, Div 2, GP ABCD T6...T4
CL I, Zone 2, AEx nA IIC T6 ... T4 Gc
Ex nA IIC T6 ... T4 Gc
CL I, Div 2, GP ABCD, T6...T4
Ex nA IIC T6 ... T4 Gc
U
= 37 V DC
max
-50 °C to +85 °C
(-58 °F to +185 °F) temperature
class T4
-50 °C to +70 °C
(-58 °F to +158 °F) temperature
class T5
-50 °C to +55 °C
(-58 °F to +131 °F) temperature
class T6
U
= 30 V DC
max
-50 °C to +85 °C
(-58 °F to +185 °F) temperature
class T4
-50 °C to +75 °C
(-58 °F to +167 °F) temperature
class T5
-50 °C to +60 °C
(-58 °F to +140 °F) temperature
class T6
SITRANS TF
-50 ... +75 °C (-58 ... +167 °F)
Temperature class T4
-50 ... +45 °C (-58 ... +113 °F)
Temperature class T6
-50 ... +75 °C (-58 ... +167 °F)
Temperature class T4
-50 ... +50 °C (-58 ... +122 °F)
Temperature class T6
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Display
-40 ... +85 °C (-40 ... +185 °F)
Temperature class T4
1)
-40 ... +55 °C (-40 ... +131 °F)
Temperature class T6
1)
-40 ... +85 °C (-40 ... +185 °F)
Temperature class T4
1)
-40 ... +60 °C (-40 ... +140 °F)
Temperature class T6
1)