Siemens SITRANS TH100 Operating Instructions Manual page 102

Temperature transmitter with 4to 20 ma/hart
Table of Contents

Advertisement

Connecting
6.10 Connect M12 cable socket to the cable
In devices where a plug is already mounted on the enclosure, the connection is made via a cable
socket.
1. Thread the parts of the cable socket as described by the manufacturer of the cable socket.
2. Strip approximately 18 mm of the bus cable
3. Twist the shield.
4. Thread the shield in the insulating sleeve.
5. Draw 8 mm of shrink sleeve over the cable, wires and shield up to the reference edge
6. Screw the cable ends and the shield in the pin insert.
7. Fasten the parts of the cable socket as described by the manufacturer.
Figure 6-10
Assignment
Layout for M12 device plug
102
Preparing the connecting cable
Reference edge for stripping
Reference edge for the dimension spec‐
ifications for cable assembly
M12 x 1 thread
Positioning catch
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
.
Insulating sleeve over the shield
Shrink sleeve
Assignment diagram M12-cable socket
Positioning slot
Operating Instructions, 05/2020, A5E41864807-AB
.