Top Vent - Horizontal Termination
One Elbow
V Minimum
COSMO42-IFT-B
90° Elbow
Not Allowed
1 ft.
305 mm
1 ft.
2 ft.
610 mm
5 ft.
3 ft.
914 mm
8 ft.
4 ft.
1.2 m
10 ft.
5 ft.
1.5 m
14 ft.
CAUTION: The SLP-HRC-SS termination caps are
not approved for use with these models. May lead to
elevated glass temperature that may cause tempered
glass breakage.
Note: Use SLP Series
components only.
Figure 4.12
Heat & Glo • COSMO32-IFT-B, COSMO36-IFT-B, COSMO42-IFT-B Installation Manual • 2619-980 Rev. G • 7/20
H
Maximum
1
COSMO36-IFT-B
Not Allowed
305 mm
1 ft.
305 mm
1.5 m
5 ft.
2.4 m
8 ft.
3.0 m
10 ft.
4.3 m
14 ft.
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
COSMO32-IFT-B
1 ft.
305 mm
2 ft.
610 mm
1.5 m
5 ft.
1.5 m
2.4 m
8 ft.
2.4 m
3.0 m
15 ft.
4.6 m
4.3 m
H MAX. =15 ft. (4.6 m)
V + H MAX. = 40 ft. (12.2 m)
Note: There MUST be a 25% reduction
in total H when using SLP-FLEX Series
(6-5/8 inch) vent except when using
the simple up and out installation. See
Figure 4.10.
H
1
V
1
27