Clearance To Combustibles; Mantels; Hearth - Vermont Castings DVRT41 Homeowner's Installation And Operating Manual

Direct vent gas fireplace
Table of Contents

Advertisement

DVRT41 Direct Vent Gas Fireplace

Clearance to Combustibles

Top of unit to ceiling ................................. 36" (914mm)
Front of unit to combustibles ................... 36" (914mm)
Appliance
Top of standoff ........................................ 0" (0mm)
Bottom ..................................................... 0" (0mm)
Side ......................................................... 0" (0mm)
Back ......................................................... 0" (0mm)
Venting
Concentric sections of DV Vent ................... 1" (25mm)
Nonconcentric sections of DV Vent
Sides and bottom .................................. 1" (25mm)
Top ........................................................ 2" (51mm)

Mantels

The height that a combustible mantel is fitted above
the fireplace is dependent on the depth of the mantel.
This also applies to the distance between the mantel
leg (if fitted) and the fireplace.
For the correct mounting height and widths, refer to
Figures 4a, 4b and the Mantel Chart below.
The distances and reference points are not affected by
the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at
any height and width around the appliance. When
using paint or lacquer, it must be heat resistant to
prevent discoloration.
V
W
X
Y
Z
A
B
C
D
E
Bottom of Door Trim
Mantel Chart
Mantel Shelf
Ref.
or Breast Plate Ref. of Comb. Chamber
Depth
V
10" (254mm)
W
8" (203mm)
X
6" (152mm)
Y
4" (101mm)
Z
2" (51mm)
Fig. 4a Combustible mantel minimum installation.
6
Maintain minimum 3/4"
(19mm) clearance to
combustible
Fireplace
Louvre
Assembly Top
Top of Combustion
Chamber
CFM146
Mantel from Top
A
19" (483mm)
B
17" (432mm)
C
15" (381mm)
D
13" (330mm)
E
11" (279mm)
Black
Surround
Face
Mantel
Leg
CFM164a
Side of
Combustion Chamber
Mantel
Ref.
Leg Depth
F
10" (254mm)
G
8" (203mm)
H
6" (152mm)
I
4" (101mm)
J
2" (51mm)
Fig. 4b Combustible mantel leg minimum installation.

Hearth

A hearth is not mandatory, but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12" (305mm) or more from
the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory that the outer walls be insu-
lated to conform to applicable insulation
codes.
J
I
H
G
K
L
M
N
O
CFM170
Mantel Leg from Side
Ref.
of Comb. Opening
K
11 " (292mm)
L
9 " (241mm)
M
7 " (191mm)
N
5 " (140mm)
O
3 '" (89mm)
10006740
F