Output Parameters - Bosch Rexroth IndraControl S67 Series Application Description

Digital module 8 outputs
Hide thumbs Also See for Rexroth IndraControl S67 Series:
Table of Contents

Advertisement

44/69
Bosch Rexroth AG
Parameterization
9.3

Output Parameters

Rexroth IndraControl S67 Digital Module 8 Outputs – 2.0 A (4×M12)
Global diagnostics
Description
Undervoltage U
LS
Disabling the outputs. In case of an undervoltage of U
U
, the module outputs are disabled. Machine components
LS
can be set to a dangerous state and endanger personnel as
well as machine.
If there is an undervoltage at the module of the logic and sen‐
sor supply (U
nostics is sent to the field bus coupler. The F-LED of the mod‐
ule is lit
Undervoltage U
A
Disabling the outputs. In case of an undervoltage of U
U
, the module outputs are disabled. Machine components
LS
can be set to a dangerous state and endanger personnel as
well as machine.
If there is an undervoltage of the actuator supply (U
the module, the outputs are disabled and a diagnostics is sent
to the field bus coupler. The F-LED of the module is lit
Tab. 9-1:
Global diagnostics of the module
Channel diagnos‐
Description
tics
Short circuit/actua‐
The module detected a short circuit or overload at the corre‐
tor overload
sponding channel (1 – 8) (only active in case of an active ac‐
tuator output)
Actuator interrup‐
The module detected an interruption or overload at the corre‐
tion
sponding channel (1 – 8) (only active in case of an active ac‐
tuator output)
Overtemperature
The module detected overtemperature at the corresponding
channel (1 – 8) (only active in case of an active actuator out‐
put)
Tab. 9-2:
Channel diagnostics of the module
If the S-BUS is interrupted, the S67-DO8-M12-2A module auto‐
matically goes into the STOP state. The module outputs are disa‐
bled.
An overview on the parameters to be set for the digital outputs is given in the
following table.
Bold parameters are default values.
DOK-CONTRL-S67DO8M122A-AP03-EN-P
WARNING
< 18 V), the outputs are disabled and a diag‐
LS
WARNING
and/or
A
and/or
A